MODULAR SUNWAY TG
TE OD
INSTALLATION GUIDE
62/
139
Rev. 03
– 01/06//2018
Terminal
Position
Name
Function and electrical specifications
A
C.
X
6
1
OUT1 RELAY1-
COM
Programmable output 1, DC1 converter module
Refer to the Programming Guide for the isolation loss
of the PV field connected to the DC1 module.
Voltage-free contacts: 230Vac/10A - 30Vdc/1
2
OUT1 RELAY1-NC
3
OUT1 RELAY1-NO
4
OUT1 RELAY2-
COM
Programmable output 1, DC2 converter module
Refer to the Programming Guide for the isolation loss
of the PV field connected to the DC2 module.
Voltage-free contacts: 230Vac/10A - 30Vdc/10A
5
OUT1 RELAY2-NC
6
OUT1 RELAY2-NO
7
OUT2 RELAY1-
COM
Programmable output 2, DC1 module converter
Refer to the Programming Guide.
Factory setting: relay energized with converter in
section DC1 running.
Voltage free-contacts: 230Vac/10A - 30Vdc/10A
8
OUT2 RELAY1-NC
9
OUT2 RELAY1-NO
10
OUT2 RELAY2-
COM
Programmable output 2, DC2 module converter
Refer to the Programming Guide.
Factory setting: relay energized with converter in
section DC2 running.
Voltage-free contacts: 230Vac/10A - 30Vdc/10A
11
OUT2 RELAY2-NC
12
OUT2 RELAY2-NO
13
EMERGENCY
STOP
Emergency signal
When short-circuiting the two terminals, the inverter
stops in an emergency.
Leave unconnected if not used.
Connect to a voltage-free contact.
The emergency stops causes the following:
•
Stops the inverter.
•
Opens the PV-side disconnect switch.
•
Opens the grid-side switch.
14
15
EXTERNAL GRID
INTERFACE