85
Here, cell fault includes: phase loss, overheat, IGBT failure, optical fiber fault, over voltage, under voltage, and
power fault.
Heavy fault alarm is divided into drive heavy fault and cell heavy fault. When heavy fault alarms, the system
issues a warning signal, failure instructions and command the high-voltage break to open (the high-voltage power
break will work automatically). At the same time, it records the failure and MV breaking instructions, so even when
the fault disappears, the instructions and MV breaking command remains. The VFD restores ready status after
troubleshooting and resetting.
8.3 Normal Problems processing
When VFD failure occurs, the HMI will display related information. According to this information, the operator can
take appropriate measures to troubleshoot the fault.
8.3.1 VFD trip analysis
Please refer to Figure 8.1 to analyze VFD trip reason.
Table 8-1 Check before VFD power on
VFD trip
Instantaneous trip
when power on
1. Check switch
cabinet protection
2. Check interlock
with DCS
3.Refer to table 8-1
1. Abnormal situation,once
happed, check whole system
including VFD (VFD control
system), switch cabinet,
bypass cabinet, all interlock
loops, etc.
2. Refer to table 8-1
HMI display
fault?
HMI display
fault?
Refer to 8.3.2
NO
NO
YES
YES
System ready trip
Start- up
process trip