4.1 Cable Selection
4.1.1 Power Cable Selection
Selection of power cable should strictly observe related norms and meet the following requirements:
●
Current carrying capacity
●
Cable manufacturer standard
●
Installation and laying modes
●
Voltage drop caused by cable length
●
Power industry standard
●
EMC standard
Wiring & Terminal Definition
Chapter 4
●
Armored cables with shielding effect is recommended for MV cable used between the VFD and the motor, it can
prevent the rodent damage and meet the requirement of EMC.
●
If the whole section area is less than 50% of the section area of single-phase conductor, a grounding
cable is needed to prevent the shield over-current produced by potential difference of grounding grid.
●
Section area of grounding cables should be bigger than 16mm
2