Table 4-3 Terminal row below the interface board digital value definition
Terminal
number
Name
Status
Type
Capacity
Notes
XS11T:1
XS11T:2
MV indication1
Effective when close
DO/NO
8A/250VAC
MV ready, close
XS11T:3
XS11T:4
MV indication 2
Effective when close
DO/NO
8A/250VAC
XS11T:5
XS11T:6
Fault indication 1
Effective when close
DO/NO
8A/250VAC
Light fault flashing (1s 1 cycle, 0.5s on/0.5s
off), heavy fault always on
XS11T:7
XS11T:8
Fault indication 2
Effective when close
DO/NO
8A/250VAC
XS11T:9
XS11T:10
Running signal1
Effective when close
DO/NO
8A/250VAC
VFD running, close
XS12T:1
XS12T:2
Running signa2
Effective when close
DO/NO
8A/250VAC
XS12T:3
XS12T:4
Close permit 1
Effective when close
DO/NO
8A/250VAC When the “control status” in the HMI
function menu is normal status and VFD has
no heavy fault output, close
XS12T:5
XS12T:6
Close permit 2
Effective when close
DO/NO
8A/250VAC
XS12T:7
XS12T:8
Open signal 1
Effective when close
DO/NC
8A/250VAC When the “control status” in the HMI
function menu is debug status and VFD has
heavy fault output, close
XS12T:9
XS12T:10
Open signal 2
Effective when close
DO/NC
8A/250VAC
XS13T:1
XS13T:2
Heavy fault
output
Effective when close
DO/NO
8A/250VAC Heavy fault, close
XS13T:3
XS13T:4
Heavy fault
output
Effective when open
DO/NC
8A/250VAC Heavy fault, open
XS13T:5
XS13T:6
Top fan start 1
Effective when close
DO/NO
8A/250VAC
When requiring to start top fans, close
XS13T:7
XS13T:8
Top fan start 2
Effective when close
DO/NO
8A/250VAC
XS13T:9
XS13T:10
Excitation start
Effective when close
DO/NO
16A/250VAC When requiring to start excitation, close
XS14T:1
XS14T:2
Remote control
indication
Effective when close
DO/NO
16A/250VAC VFD control mode is remote control, close
XS14T:3
XS14T:4
Cabinet door
alarm
Effective when close
DO/NO
16A/250VAC Cabinet door open, close
XS14T:5
XS14T:6
Power cell
overheat alarm
Effective when close
DO/NO
16A/250VAC Power cell cabinet over heat, close
XS14T:7
XS14T:8
Fan fault alarm
Effective when close
DO/NO
16A/250VAC Fan fault, close
XS14T:9
XS14T:10
Transformer over
temp alarm
Effective when close
DO/NO
16A/250VAC Transformer over temp, close
XS15T:1
XS15T:2
Spare
Effective
DO/NO
16A/250VAC Spare contact
XS15T:3
XS15T:4
Phase lock
success
Effective when close
DO/NO
16A/250VAC
During synchronous transfer switch, when
the output voltage and network voltage
difference is within the permit range, close
(phase max. tolerance ±5°, amplitude Max.
Tolerance±2% )