59
Parameter name
Description
Value
Unit
Default
value
Change
Baud rate
The setting of communication baud rate in Upper
communication
0
:
1200
1
:
2400
2
:
4800
3
:
9600
4 : 19200
5 : 38400
No
3
○
Fan control
Set the fan start/stop
0
:
Stop
1
:
Start
No
0
○
Light fault energized
When the VFD has a light fault, whether or not
to allow the VFD energized on MV to continue to
work
0
:
Disable
1 : Enable
No
0
○
Jump frequency 1L
Lower limit of jump frequency 1, see 5.3.11
0.00~80.00
Hz
51.00
○
Jump frequency 1U
Upper limit of jump frequency 1,see 5.3.11
0.00~80.00
Hz
51.00
○
Jump frequency 2L
Lower limit of jump frequency 2, see 5.3.11
0.00~80.00
Hz
51.00
○
Jump frequency 2U
Upper limit of jump frequency 2,see 5.3.11
0.00~80.00
Hz
51.00
○
Input voltage
coefficient
Correction coefficient of input voltage value
If the measured input voltage is smaller than the
true value, the value should be adjusted higher;
otherwise, the input voltage should be reduced
50~200
No
100
○
Max. set current
The Max. value of given current signal at the site,
corresponding to the Max. frequency (or closed loop
control to the given quantitative 100%) Notes: When
the analog given is voltage signal, theMax. value of
a given voltage is adjusted by this parameter.
10.00~25.00
mA
20.00
○
Min. set current
The Min. value of given current signal at the site,
corresponding to 0Hz (or closedloop control to the
given quantitative 0%) Notes: When the analog
given is voltage signal, theMax. value of a given
voltage is adjusted by this parameter.
0.00~8.00
mA
4.00
○
DI set 1
The set frequency when PLC speed 1 closed
0.00~80.00
Hz
10.00
○
DI set 2
The set frequency when PLC speed 2 closed
0.00~80.00
Hz
20.00
○
DI set 3
The set frequency when PLC speed 3 closed
0.00~80.00
Hz
30.00
○
Power loss shielding
time delay
High voltage power loss occurs, time delay of
shielding failure of high voltage power loss
1~100
S
1
◎