Step
Key
PV
SV
Explanation
Remark
1
SET
-cd-
1000 Instrumentation is in parameters setting state
2
△
or
▽
-cd-
1005 Input password (1005) for parameters setting
I f p a s s w o r d i s w r o n g
,
parameters cannot be set.
3
SET
-Ob-
90.0
Initially target temperature of air blower starting
is 90.0
℃
Setting range is
0.0~200.0
A l l o f t h e
parameters
c a n b e
e d i t e d b y
△
or
▽
4
SET
-dF-
10.0
Initially start backlash of air blower is 10.0
℃.
In other words, the temperature of air blower
starting is T
>
100.0
℃
(90.0+10.0), and the
temperature of air blower turning off is T
<
80.0
℃
(90.0-10.0).
Setting range
of backlash
is0.0~15.0
5
SET
-AH- 150.0
Initially excess temperature tripping of air
blower is 150.0
℃
.
Setting range is
0.0~200.0
6
SET
-AL- 130.0
Initially over temperature alarm of air blower is
130.0
℃
.
7
SET
Make sure edited parameter correct; quit parameters setting
state, return to
(1) Parameter Setup Table
temperature controller from maximum value display to patrol display in each phase or vice versa.
Note: In key operation, if no key is pressed, the temperature controller will return to normal working mode
automatically in about 100 seconds while the setting will become invalid.
2. Parameter setting
Step Key
PV
SV
Explanation
Remark
1
SET
-cd-
1000
Instrumentation is in
parameters setting state
2
△
or
▽
-cd-
1008
Input password (1008) for
parameters setting
If password is wrong
,
parameters
cannot be set.
3
SET
Temperature
of phase A
A0.0
Enter phase A compensation
value set state , and
the original phase A
compensation value is 0.0
℃
The compensation value can be
set as positive compensation or
negative compensation, and the set
range is 0 ~ ±19.9
4
△
or
▽
Phase A
compensated
temperature
display value
A1.5
Set phase A compensation
value to 1.5
℃
5
According
to the same
steps to set
phase B, C
compensation
value
Operation and display are the same as phase A
6
SET
Confirm the compensation value after setting, the
instrument exits the compensation value setting
state, return to the normal working state