33
Terminal
number
Name
Status
Type
Notes
XS1T:1
XS1T:10
Level
forward start-
stop/ pulse
start
Close/
open
DI/ level or
pulse signal
Valid when the control mode in HMI function menu set to “remote control”.
The “remote start/stop mode” set correspond to 2 types of input mode:
level forward start-stop: forward start when close, stop when open (set to
level mode)
pulse start: close then open (pulse width more than 500ms), start (remote
start/stop mode set to pulse mode)
XS1T:1
XS1T:9
Level
reverse start-
stop/pulse
stop
Close/
Open
DI/level or
pulse signal
Valid when the control mode in HMI function menu set to “remote control”.
The “remote start/stop mode” set correspond to 2 types of input mode:
level reverse start/stop: reverse start when close, stop when open,(set to
level mode, VFD reserves set to permit
Pulse stop, close then open (pulse width more than 500ms), stop (remote
start/stop mode set to pulse mode)
XS1T:1
XS1T:8
Emergency
stop
Effective
when open
DI/NC
Level signal
open,the output blocked, motor free stop
XS1T:1
XS1T:7
Speed 1
Effective
when
close
DI/NO
Level signal
”HMI function “Running mode” is open loop, “set mode” valid at switch
mode, after close, the set frequency corresponds to “switch set 1”, “switch
set 2”, and “switch set 3”
XS1T:1
XS1T:6
Speed 2
Effective
when
close
XS1T:1
XS1T:5
Speed 3
Effective
when
close
XS1T:1
XS1T:4
Remote
control enable
Effective
when
close
DI/NO
Level signal
HMI function item “control mode set from remote” valid when permit, after
close, VFD control mode will be remote control
XS1T:1
XS1T:3
External
reset
Effective
when
close
DI/NO
Pulse signal
After close, when heavy fault, the control system will be reset, or the HMI
will be reset when running (equal to the function of the reset button on the
cabinet door)
XS2T:1
XS2T:10
MV break
Effective
when
close
DI/NO
Pulse signal
After close, MV input power will be cut (equal to MV break button on the
cabinet door)
XS2T:1
XS2T:9
MV break
Effective
when
close
DI/NO
Pulse signal
After close, MV input power will be cut (equal to MV break button on the
cabinet door)
XS2T:1
XS2T:8
Switch
activated
Effective
when
close
DI/NO
Pulse signal
Valid when HMI function item “switch permit” set to enable, after close, VFD
output frequency will be increased to network frequency, and phase lock.
XS2T:1
XS2T:7
Excitation
ready
Effective
when
close
DI/NO
Pulse signal After excitation ready, the contact will close (used on synchronous motor)
XS2T:1
XS2T:6
Excitation
running
Effective
when
close
DI/NO
Pulse signal
Excitation running, the contact close (used on synchronous motor)
XS2T:1
XS2T:5
Excitation
fault
Effective
when
close
DI/NO
Pulse signal
Excitation fault, the contact close (used on synchronous motor)
XS4T:1
XS4T:2
Excitation
feedback
4
~
20mA
AI/
current
Excitation current feedback to I/O board, VFD will do relevant adjustment.
Table 4-2 Definition of terminal row above the interface board