Parameter lists
AO FB:
SHED_OPT (27)
Storage class S; read/write capability r/w; supported modes ALL
Behavior upon exceeding the monitoring time (see SHED_RCAS in the Resource Block)
Monitoring of the connection between fieldbus host system and AO Function Block in RCAS
mode. When the monitoring time has elapsed, AO Function Block switches from the RCAS
mode to the selected operating mode.
The action to be taken after the fault state ends is also determined.
•
[UNINITIALIZED]
•
NORMAL SHED_NORMAL RETURN · On failure of remote connection, change to next
possible mode until RCAS mode is restored.
•
NORMAL SHED_NO RETURN · On failure of remote connection, change to next
possible mode. The block remains in this mode.
•
SHED TO AUTO_NORMAL RETURN · On failure of remote connection, change to AUTO
mode until RCAS mode is restored.
•
SHED TO AUTO_NO RETURN · On failure of remote connection, change to AUTO
mode. No attempt is made to restore the mode and the block remains in AUTO mode.
•
SHED TO MANUAL_NORMAL RETURN · On failure of remote connection, change to
MAN mode until RCAS mode is restored.
•
SHED TO MANUAL_NO RETURN · On failure of remote connection, change to MAN
mode. No attempt is made to restore the mode and the block remains in MAN mode.
•
SHED TO RETAINED TARGET_ NORMAL RETURN · On failure of remote connection, the
block attempts to attain the retained target mode until RCAS mode is restored.
•
SHED TO RETAINED TARGET_NO RETURN · On failure of remote connection, the block
sets the target mode to the retained target mode.
Note:
This parameter is only active in RCAS mode in the AO Function Block.
If the value is set to UNINITIALIZED, the AO Function Block cannot be placed in the RCAS
mode.
AO FB:
SIMULATE (10)
Storage class D; read/write capability r/w; supported modes ALL
Simulation of the process variable PV of the block (value and status)
Code 48 F3
Note:
During simulation, OUT is not transmitted to the Transducer Block; the block retains
the last valid value received before simulation was activated.
The simulation can only be activated when SIMULATE ACTIVE is set in the BLOCK_ERR
parameter of the Resource Block.