84
KH 8384-5 EN
Parameter lists
AO FB:
CHANNEL (22)
Storage class S; read/write capability r/w; supported modes O
Assignment of the output of AO
Function Block
and the logical hardware channels
(Transducer Block).
• [3]
Note:
Set CHANNEL to 3 to start up the AO Function Block. This allows it to be assigned to
AO TRD.
AO FB:
FSTATE_TIME (23)
Storage class S; read/write capability r/w; supported modes ALL
Fault state time [s]
Time between an error in the set point valid for the AO
Function Block
in the current
operating mode is detected and failure action is triggered.
• [0]
Note:
Failure action is triggered if the error persists after this time has elapsed. The fault
state of the AO Function Block is determined in the IO_OPTS parameter of this block.
AO FB:
FSTATE_VAL (24)
Storage class S; read/write capability r/w; supported modes ALL
Fault state value for the AO Function Block when failure action is triggered.
•
Value and range from PV_SCALE ±10 %, [0]
Note:
The value is used if the FAULT STATE TO VALUE option is selected in the IO_OPTS
parameter.
AO FB:
GRANT_DENY (13)
· This parameter is not supported.
AO FB:
IO_OPTS (14)
Storage class S; read/write capability r/w; supported modes O
Selects the input/output behavior of the AO Function Block.
•
SP-PV TRACK IN MAN · SP tracks PV in MAN mode (Actual Mode)
•
SP-PV TRACK IN LO · SP tracks PV in LO mode (Actual Mode)
•
SP TRACK RETAINED TARGET · SP tracks RCAS_IN or CAS_IN depending on the preset
target mode in LO or MAN mode (actual mode). This option has priority over SP-PV
TRACK IN MAN/LO.
•
INCREASE TO CLOSE · Inverts the output value to the Transducer Block (corresponds to
the direction of action)