KH 8384-5 EN
77
Parameter lists
AO TRD: XD_FSTATE_VAL_D (53)
Storage class S; read/write capability r/w; supported modes O/M/A
Discrete fault state value to which the valve moves when the AO Transducer Block is in the
O/S mode and the action on fault detection has been selected in the XD_OOS_OPTS
parameter.
•
[0], 10 - 0 %1 - 100 %
AO TRD: XD_OOS_OPT (54)
Storage class S; read/write capability r/w; supported modes O/M/A
Action when the AO Transducer Block is in the O/S mode
• [Hold last value]
• Fail-safe position
•
Fault state value (XD_FSTATE_VAL)
AO TRD: Y_HYST_MIN_TIME_DISTANCE (160)
Storage class S; read/write capability r/w; supported modes O/M/A
Statistical information > Drive signal diagram > Hysteresis
Time until test (d5) is repeated
• 0 to 24 h, [1 h]
AO TRD: Y_HYST_TESTINFO (162)
Storage class D; read capability r
Statistical information > Drive signal diagram hysteresis (d5 test): test status
AO TRD: Y_HYST_TEST_INFO (186)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test): test status
AO TRD: Y_HYST_TEST_PROGRESS (187)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test): progress of test in %
AO TRD: Y_HYST_TEST_TIME_STAMP (185)
Storage class D; read capability r
Tests > Drive signal diagram hysteresis (d2 test): time stamp for reference value recording
AO TRD: Y_HYST_TOLERANCE_BAND (161)
Storage class D; read/write capability r/w; supported modes O/M/A
Statistical information > Drive signal diagram > Hysteresis
Tolerance band of test (d5) (the test is canceled when the value leaves the tolerance band)