44
KH 8384-5 EN
Parameter lists
AO TRD: ALERT_KEY (4)
Storage class S; read/write capability r/w
ID number of the plant section
• 1 to 255, [0]
May be used by the fieldbus host system to sort alarms and events.
Note:
'0' is not permissible and will be rejected when transferring data to the device (error
alarm).
AO TRD: ANALYSIS_OPEN_CLOSE (147)
Storage class D; read capability r
Statistical information > Open/Close
Reference analysis and the last two test analyses (
u
EB 8389 (EXPERTplus valve
diagnostics)
•
TIME_STAMP_RISING/FALLING
•
BREAK_AWAY_TIME_RISING/FALLING
•
TRANSIT_TIME_RISING/FALLING
•
VALVE_END_POSITION_RISING/FALLING
AO TRD: APPLICATION_TYPE_OC_CONTROL (144)
Storage class S; read/write capability r/w; supported modes O/M/A
Application type (valve)
•
Control Valve
•
Open/Close (on/off) Valve
AO TRD: AUTOMATIC_TEST_STATUS (175)
Storage class S; read/write capability r/w; supported modes O/M/A
Status of active test: drive signal diagram steady (d1 test)
Drive signal diagram hysteresis (d2 test)
Static characteristic (d3 test)
Partial stroke test (PST) (d4 test)
AO TRD: BINARY_INPUT_2 (111)
Storage class D; read capability r
State of DI2 Function Block
The value issued depends on CONFIG_BINARY_INPUT_2.