111
Parameter lists
PID FB:
SP_RATE_DN (19)
Storage class S; read/write capability r/w; supported modes ALL
Set point downward rate limit in AUTO mode
• [3402823466 x 10
38
]
Note:
if '0' is entered, the set point is used. Speed limitation for control blocks is only
active in AUTO mode.
PID FB:
SP_RATE_UP (20)
Storage class S; read/write capability r/w; supported modes ALL
Set point upward rate limit in AUTO mode
• [3402823466 x 10
38
]
Note:
if '0' is entered, the set point is used. Speed limitation for control blocks is only
active in AUTO mode.
PID FB:
ST_REV (1)
Storage class S; read capability r
Static revision number (PID)
Note:
The revision number is incremented with each change of a static parameter in the
block.
PID FB:
STATUS_OPTS (14)
Storage class S; read/write capability r/w; supported modes O
Status options to determine status handling and processing
•
[UNINITIALIZED]
•
IFS IF BAD IN · Fault state of the downstream AO Function Block is triggered when the
controlled variable IN changes the status to BAD.
•
IFS IF BAD CAS_IN · Fault state of the downstream AO Function Block is triggered when
the external set point CAS_IN changes the status to BAD.
•
USE UNCERTAIN AS GOOD · The UNCERTAIN status is used as GOOD
•
TARGET IN MANUAL IF BAD IN · Transition to MAN mode if the controlled variable
changes the status to BAD
PID FB:
STRATEGY (3)
Storage class S; read/write capability r/w; supported modes ALL
Permits strategic grouping and thus faster processing of blocks
• [0]
Blocks are grouped by entering the same number in the STRATEGY parameter of each
block.
Note:
These data are neither checked nor processed by the PID Function Block.