KH 8384-5 EN
45
Parameter lists
AO TRD: BLOCKING_POSITION (124)
Storage class S; read/write capability r/w; supported modes O/M/A
Blocking position
Code 35
Distance to CLOSED position (0 % position)
Note:
Only necessary with SUB initialization mode.
AO TRD: BLOCK_ALM (8)
Storage class D; read/write capability r/w
Current block state with details on all configuration, hardware or system problems in the
block including date and time stamp.
AO TRD: BLOCK_ERR (6)
Storage class D; read capability r
Active block errors
Code 48 S2
•
SIMULATE ACTIVE · Simulation jumper active, simulation possible
•
OUT OF SERVICE · Block mode is out of service
•
LOST STATIC DATA · Data loss in EEPROM
•
DEVICE NEEDS MAINTENANCE SOON · Maintenance required soon. This message
triggers a block alarm (BLOCK_ALM) in the AO TRD Block.
•
DEVICE NEEDS MAINTENANCE NOW · Maintenance required now. This message
triggers a block alarm (BLOCK_ALM) in the AO TRD Block.
Note:
The assignment of error or diagnostic alarms to the desired function block is made
using the ERROR_OPTION parameters in the Transducer Block.
AO TRD: CHARACTERIZATION (91)
Storage class S; read/write capability r/w; supported modes O/M/A
Characteristic selection
Code 20
1 Linear
2
Equal percentage
3
Equal percentage reverse
4
SAMSON butterfly linear
5
SAMSON butterfly equal percentage
6
VETEC rotary linear
7
VETEC rotary equal percentage
8 Segmented ball valve linear
9 Segmented ball valve (equal) percentage
10
User defined
Definition using AO TRD (CUSTOM_CURVE_XY_FLOAT (63))