KH 8384-5 EN
29
Parameter lists
RES:
BLOCK_ERR (6)
Storage class D; read capability r
Active block errors
Code 48 S2
•
SIMULATE ACTIVE · Simulation jumper active, simulation possible
•
OUT OF SERVICE · Block mode is out of service
•
LOST STATIC DATA · Data loss in EEPROM
•
DEVICE NEEDS MAINTENANCE SOON · Maintenance required soon. This message
triggers a block alarm (BLOCK_ALM) in the Resource Block.
•
DEVICE NEEDS MAINTENANCE NOW · Maintenance required now. This message
triggers a block alarm (BLOCK_ALM) in the Resource Block.
Note:
The assignment of error or diagnostic alarms to the desired function block is made
using the ERROR_OPTION parameters in the Transducer Block.
RES:
BUS_ADDRESS (78)
Storage class D; read capability r
Bus address
Code 46
• 0 to 255, [248]
RES:
CLR_FSTATE (30)
Storage class D; read/write capability r/w; supported modes O/A
Deactivation of the fault state of the AO Function Block
RES:
CONDENSED_STATE (81)
Storage class D; read capability r
Displays the current condensed state according to NAMUR Recommendation NE 107
RES:
CONFIRM_TIME (33)
Storage class S; read/write capability r/w; supported modes O/A
Confirmation time for event report
If the device does not receive a confirmation within this period of time, the event report is
sent again.
•
[640000 ms]
RES:
CYCLE_SEL (20)
Storage class S; read/write capability r/w; supported modes O/A
Block execution method determined by the fieldbus host system
• [Scheduled]
•
Block Execution · Block execution completed
•
Manuf Specific · Not analyzed
Note:
The execution method is selected directly in the fieldbus host system.
Содержание FOUNDATION 3730-5