KH 8384-5 EN
Parameter lists
•
SHED TO AUTO_NORMAL RETURN · On failure of remote connection, change to AUTO
mode until RCAS or ROUT mode is restored.
•
SHED TO AUTO_NO RETURN · On failure of remote connection, change to AUTO
mode. No attempt is made to restore the mode and the block remains in AUTO mode.
•
SHED TO MANUAL_NORMAL RETURN · On failure of remote connection, change to
MAN mode until RCAS or ROUT mode is restored.
•
SHED TO MANUAL_NO RETURN · On failure of remote connection, change to MAN
mode. No attempt is made to restore the mode and the block remains in MAN mode.
•
SHED TO RETAINED TARGET_ NORMAL RETURN · On failure of remote connection, the
block attempts to attain the retained target mode until RCAS or ROUT mode is restored.
•
SHED TO RETAINED TARGET_NO RETURN · On failure of remote connection, the block
sets the target mode to the retained target mode.
Note:
This parameter is only active in RCAS and ROUT modes in the PID Function Block. If
the value is set to UNINITIALIZED, the PID Function Block cannot be placed in the RCAS or
ROUT mode.
PID FB:
SP (8)
Storage class N; read/write capability r/w; supported modes O/M/A
Set point w in AUTO mode (value and status)
Code 48 P4/5
•
Value and range from PV_SCALE ±10 %
PID FB:
SP_HI_LIM (21)
Storage class S; read/write capability r/w; supported modes ALL
Upper set point limit
•
Value and range from PV_SCALE ±10 %, [100]
Note:
Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.
PID FB:
SP_LO_LIM (22)
Storage class S; read/write capability r/w; supported modes ALL
Lower set point limit
•
Value and range from PV_SCALE ±10 %, [0]
Note:
Adapt this value accordingly if the end-of-scale value in the PV_SCALE parameter is
changed.