Parameter lists
AO TRD: SIGNAL_ACTION (34)
Storage class S; read/write capability r/w; supported modes O/M/A
Direction of action of the set point w in relation to the travel/angle x
Code 7
AO TRD: SKR (192)
Storage class D; read capability r
Tests > Static characteristic: display
•
STAT_KENNL_R_TEST_INFO · Current status of the test
•
STAT_KENNL_R_STEP_HEIGHT · Step height
•
STAT_KENNL_R_MIN_DEAD_BAND · Smallest dead band measured
•
STAT_KENNL_R_AVERAGE_DEAD_BAND · Average dead band measured
•
STAT_KENNL_R_MAX_DEAD_BAND · Largest dead band measured
•
STAT_KENNL_R_PROGRESS_FLAG · Current progress of the test
AO TRD: SKW (193)
Storage class S; read/write capability r/w
Tests > Static characteristic: enter values
•
STAT_KENNL_W_START_VALUE · Start value of valve position x
•
STAT_KENNL_W_END_VALUE · End value of valve position x
•
STAT_KENNL_W_DELAY_TIME · Delay time after step
•
STAT_KENNL_W_TURN_BACK_VALUES · Number of measured values recorded before
changing the testing direction
AO TRD: SSAF (133)
Storage class D; read/write capability r/w
Execute/end various EXPERTplus tests
•
Reference tests (d1, d2)
• Data logger
• Tests (d1 to d6 and d9)
AO TRD: STOP_HI (27)
Storage class S; read/write capability r/w; supported modes O/M/A
Travel/angle upper limit
Code 11
•
50 … 120 %, [100 %]
Note:
The characteristic is not adapted. The tight-closing function has priority.