4.2.
DEFINITION AND STRUCTURE.
4.2.1. Nomenclature.
Equipment
SLC-10-CUBE3+ LBT-P2 B1 0/62AB147 AWCO “EE550714-2”
External batteries or extended back up times
MOD BAT CUBE3+ 0/2x62AB147/213 100A AWCO “EE550714-2”
EE*
Particular client specifications.
CO
“Made in Spain” marking in UPS and packaging (for customs).
W
Neutral brand equipment.
A
For single phase mains 115.. 133 V or three phase 3x200.. 3x230 V.
147
Last three characters of the battery code
(*)
.
AB
Letters of the battery family
(*)
.
62
Quantity of batteries in one string
(*)
.
0/
Ready for standard back up time, no batteries installed but with the
needed accessories to install them.
/
No batteries installed but with the needed accessories to install
them. Batteries are supplied separately.
B1
Equipment with external batteries for non-standard back up time.
P2
Parallel system based on two equipments.
P3
Parallel system based on three equipments.
P4
Parallel system based on four equipments.
T
Top entry cables (160 and 200 kVA only).
B
Separate bypass line version.
L
Single phase input / single phase output setting.
M
Single phase input / three phase output setting.
N
Three phase input / single phase output setting.
Three phase input / three phase output setting.
CUBE3+ Series.
10
Power in kVA.
SLC
Brand abbreviation for UPS.
CF
Frequency converter 50/60 or 60/50 Hz (**).
EE*
Particular specifications of the client.
CO
“Made in Spain” marking in UPS and packaging (for customs).
W
Neutral brand equipment.
A
Battery set for mains 115.. 133 V or 3x200.. 3x230 V.
100A
Protection size.
213
Last three characters of the battery code type 2.
147
Last three characters of the battery code type 1.
AB
Letters of the battery family.
62
Quantity of batteries in one string.
2x
Quantity of battery strings in parallel. Omitted for one.
0/
Battery cabinet without batteries, but with the needed accessories
to install them.
S/
Battery cabinet without batteries and without the needed accesso-
ries to install them.
/
Batteries not installed at factory, but with the needed accessories.
Batteries are supplied separately.
CUBE3+ Series.
MOD BAT
Battery module or rack.
(B1) The equipment is supplied without batteries and without the accessories (bolts and electrical cables). It is foreseen that batteries
will be fitted in an external cabinet or rack. Under request a cabinet or rack and needed accessories can be supplied.
For those equipments requested with no batteries, their acquisition, installation and connection will be always done by the client and
under
his responsibility
. Nevertheless, the intervention of our
S.T.S.
can be required, in order to make all the installation and connection tasks.
Data regarding batteries like its quantity, capacity and voltage are stated in the battery label sticked beside the nameplate of the equipment,
respect this data strictly
and the polarity of the battery connection too.
In equipments with separate static bypass line, a galvanic isolation transformer has to be fit in any of both UPS power supply lines (rectifier
input or static bypass), in order to avoid a direct connection of the neutral of both lines through the internal wiring of the equipment. This is
only applicable, when both lines come from different mains, i.e.:
- Two different electrical companies.
- One electrical company and generator set, ...
(*)
Equipments with batteries for an extended back up time.
(**)
Frequency converters will not have either static bypass or manual bypass, although they have or not batteries.