![Salicru SLC Cube3+ Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/salicru/slc-cube3/slc-cube3_user-manual_3601670006.webp)
6
•
To manipulate over the connection terminals of the
equipment, which has been already connected to mains,
wait for five minutes after its complete isolation, before taking
any action in it.
2.2.1. To keep in mind.
• The UPS is supplied packaged from factory in the best way for
its transport and shipment till its new owner or receiver. It is
recommended to transport it packaged as close as possible to
its final location.
• When serious damages are observed in the packaging, and due
to its level of deterioration damages can be sensed in the con-
tents and/or the shock indicator is in RED, proceed according
to the instructions stated in the own label of transport control.
Keep the affected equipment isolated from other received
equipments, waiting the pending inspection by qualified staff.
In case it were needed to return it back to the factory or your
distributor and it were not possible to use the same packaging
due to the poor conditions of itself, contact with the appropriate
person in order to agree the way and conditions for its return.
• Respect the unpacking instructions, as well as the established
mode to remove the equipment from the pallet.
These operations require the work of at least two persons.
• The equipment has to be in vertical position always.
When moving the equipment, consider the slope of the
ground or surface and the risk of tipping.
• Be careful to not lift heavy loads without help, according to the
following recommendations:
, < 18 kg.
, 18 - 32 kg.
, 32 - 55 kg.
, > 55 kg.
• In case of an accidental equipment dropping or if the enclosure
is damaged, do not start it up under any concept. This kind of
fault can cause fire or electrical discharge. Contact with our
(S.T.S.)
.
• Some models include casters to move it till its location. They
are not designed for long distances or constant movements.
The equipments shall be guided by two persons as minimum,
which will be placed on either side and oriented to the walking
direction.
• UPSs are electronic equipments. Avoid jolting or bouncing like
those produced by moving the equipment over an uneven or
wavy surface.
• When moving an equipment from a cold place to a warm envi-
ronment and vice versa, it can cause condensation (small water
drops) in the external and internal surfaces. Before installing a
moved equipment from another place or even packaged, the
equipment will be left for a minimum time of two hours in the
new location before making any action, with the purpose of
adapting it to the new environmental conditions and avoid the
possible condensations.
The UPS has to be completely dry before starting any installa-
tion task.
• Do not store, install or expose the equipment in corrosive,
wets, warms, dusty or with conductive parts environments and
never outdoors
.
Installation location will be cooled, dry and far from heat
sources and with easy access. If possible in an environment
with temperature control.
• Avoid to locate, install or store the equipment in places with
direct sunlight or high temperatures. Batteries can be damaged
and/or make shorter its useful lifetime.
In the exceptional and long exposition case to intense heat, bat-
teries can cause filtrations, overheating or explosions, which
can cause fires, burn or other injuries. High temperatures can
also make deformation in the plastic enclosure.
• Do not obstruct the cooling grids by entering objects through
themselves or other orifices.
• Locate the equipment as close as to the power supply outlet
and loads to supply, leaving an easy access if it were needed an
urgent disconnection.
• All models with casters have four leveller parts -feet-, which are
located at each corner of the base, with the purpose of locking
and level the unit.
Loosen them with the hand until they stop with the ground.
With the help of a spanner, act on each one and loosen
them half round more against the ground.
In grounds slightly uneven, level the equipment by means of
these leveller parts.
Check that the equipment is completely immobilized.
Fortuitous pulls of the connection cables of the equipment will
indirectly be avoided, because unexpected movements will not
happen.
• Even though the interventions inside of the equipment, battery
cabinet and battery manipulation is a task
reserved to per-
sonnel with specific or qualified
knowledge only and in par-
ticular to
(S.S.T.)
, it is mandatory to immobilize the equipment
by means of the levellers parts -feet- stated in the previous
point, before doing any action.
Attention!
Risk of tipping when removing the battery
trays without stabilising the unit first.
Do not remove more than one tray together, high risk of injury
over the operators due to shock of the possible equipment fall
down and/or entrapment.
• Leave a minimum free space to cool the unit of:
25 cm at both sides.
50 cm at the rear side.
100 cm at the top side.
and 150 cm at the front side.
• It is recommended to leave an additional 75cm at both sides,
for possible interventions of the
(S.T.S.)
or the needed clear-
ance of the connection cables to facilitate the forward move-
ment of the equipment.
• Do not cut, deteriorate or manipulate the electrical cables, nei-
ther put heavy objects over them. Any of these actions could
cause a short-circuit and make a fire or electrical discharge.
Check that the electrical cables of connection, plugs and outlets
are in good conditions.
USER MANUAL