MAX100/200-OPERATION Rev200813
73
12. Values for the ‘MASTER VOLUME’ and ‘L. FLOW VOLUME’ will be displayed.
13. Press the
DECREASE
button to select the ‘SAVE AND RETURN’ item on the screen.
14. Press the
SELECT
button to update low-flow foam flow calibration. Calibration data will be automatically
recalculated and updated to match the master flowmeter reading.
15. Dialog box will be displayed to confirm that the calibration was successfully completed. If the calibration
fails, it will need to be repeated.