MAX100/200-OPERATION Rev200813
33
6. Pairing screen will be displayed and 'TEST VALVE' item will be selected. If needed, press the
SELECT
or
ON/
OFF
button to move the valve. This will confirm that the valve chosen is the correct one.
7 To proceed with pairing, press
INCREASE
or
DECREASE
button once to select 'SAVE AND RETURN'
item. Press the
SELECT
button to save the pairing and return to the valve selection menu, or press
ON/OFF
button to cancel the pairing and return to the valve selection menu.
8. In the valve list, the paired valve will be selected and its ID will match the ID of the display module. Pairing is
now complete.
Foam Class
The Foam Class setting determines the class indicated on the display. It will be either Class A or Class B.
1. Select SETUP item in the main menu. Press the
SELECT
button to access this menu.
2. Select 'FOAM CLASS' item. Enter this submenu using the
SELECT
button.
3. The display will show Foam Class choices. To change the Foam Class, press
INCREASE
or
DECREASE
button to select the desired foam class.
4. Press the
SELECT
button to apply the change. To return to the previous menu, press the
ON/OFF
button.
Foam Pump Type
NOTE
:
Foam Pump Type is normally set at the factory. However, it can be changed at any time, if there is a configuration
change, or for replacement parts.
The Foam Pump Type setting determines the pump brand and capacity used on the
AccuMax system.
1. Select SETUP item in the main menu. Press the
SELECT
button to access this menu.
2. Select 'FOAM PUMP TYPE' item. Enter this submenu using the
SELECT
button.
3. The display will show all foam pump choices. To change the foam pump
type, press
INCREASE
or
DECREASE
button to select the desired foam
pump type.
4. Press the
SELECT
button to apply the change. To return to the previous
menu, press the
ON/OFF
button.
No Foam Shutdown Delay
The No Foam Shutdown Delay setting determines the amount of time the foam
pump will run after the system runs out of foam. After this time delay, the foam pump
will shut down. NOTE: For the duration of this delay, a "NO FOAM" warning will be displayed.
1. Select SETUP item in the main menu. Press the
SELECT
button to access this menu.
2. Select 'NO FOAM SHUTDOWN ' item. Enter this submenu using the
SELECT
button.
3. The display will show a list of the time duration options. To change the No
Foam Shutdown delay, press
INCREASE
or
DECREASE
button.
4. Press the
SELECT
button to apply the change. To return to the previous
menu, press the
ON/OFF
button.