MAX100/200-OPERATION Rev200813
68
5. Operate water valve to establish water flow rate to be used for calibration.
NOTE:
For Fusion MAX200 models with water valve control. To operate water valve, press
INCREASE
or
DECREASE
buttons until ‘OPERATE VALVE’ item is selected. Use
SELECT
or
ON/OFF
buttons to move
valve toward open or close position as needed.
6. Observe water flow rate on an external flow meter. Wait for the flow reading to stabilize if necessary. Take a
reading of the actual water flow on an external meter.
7. Select the data point value entry field by pressing the
INCREASE
or
DECREASE
buttons.
8. When the data point value field is selected, enter an actual flow reading. Use the
SELECT
button to increase digit
value at cursor position,
ON/OFF
button to decrease the digit value at the cursor position,
DECREASE
button to
move cursor to next position to the right or the
INCREASE
button to previous position to the left. Decimal point
can be used only once in the value field, to remove an unwanted decimal point and change it into a number.
9. When the flow rate value is entered, press the
DECREASE
button until ‘ADD CALIBRATION POINT’ item
is selected on the screen. (Pressing and holding the
DECREASE
button will have the same effect).
10. With ‘ADD CALIBRATION POINT’ selected, press the
SELECT
button to add a calibration data point.
11. Dialog box will be displayed to confirm if a data point was accepted or rejected. Should a point get rejected, it can
be entered again. Before reentering, check if the water sensor is properly connected and make sure the entered
value is not too close to the point already entered.
12. For a single point calibration proceed to next step 13. For a multi-point calibration repeat steps 5 through 11
with different water flow rates for each entered point.
13. Press the
DECREASE
button until the ‘SAVE AND RETURN’ item is selected. Press the
SELECT
button to
save new calibration data.
14. Dialog box will be displayed to confirm if the calibration was successfully completed. If the calibration fails,
it will need to be repeated.
NOTE:
the calibration can be canceled at any time by selecting the ‘SAVE AND RETURN’ item and pressing
the
ON/OFF
button. Previous calibration data will be restored.
Foam Flow Calibration Requirements
During foam flow meters calibrations, the volume of liquid will be flowed through the components of the system
and measured. The measured volume will be then used as reference value for the remaining foam flow meters calibration.
This process will require running the hydraulic system, foam pump and injectors. The following additional equipment is
required: flowmeter device with capability of measuring liquid volume, in line valve to set back-pressure and hoses required
for connections. FoamPro offers a calibration kit P/N: 3430-0381 that features a flowmeter and back-pressure control valve.
Access to foam calibration valves will be required. Calibration can be done using water instead of foam concentrate.
1) Master Foam Flow Meter – this calibration is performed only once for the entire system. Follow instructions
for Master Foam Meter Calibration
2) Foam Flow Meter for each Injector – follow instructions for Injector Foam Flow Meter Calibration
3) Low-Flow Foam Flow Meter - this calibration is performed only once for the entire system. Follow instructions
for Injector Foam Flow Meter Calibration.
Master Foam Flow Meter Calibration
Master Foam Flow Meter the measures the total foam flow output of the foam pump. Calibration of the meter is done
by measuring volume of liquid discharged by system with an external volume meter or by collecting this liquid to graduated
containers to determine the total volume. FoamPro recommends calibration kit P/N: 3430-0381 for convenient and accurate
foam calibration.