MAX100/200-OPERATION Rev200813
70
17. When sufficient volume has been accumulated, press the
ON/OFF
button to stop flow. It may take up to 15s to
stop the flow and close all valves. When the system has stopped, the icon on the right side of the ‘START / STOP’
item will change to .
18. Record the actual total volume accumulated on an external meter.
19. Select ‘NEW VALUE’ entry field by pressing the
INCREASE
or
DECREASE
buttons.
20. When ‘NEW VALUE’ value field is selected, enter the recorded volume. Use the
SELECT
button to increase
the digit value at the cursor position, the
ON/OFF
button to decrease the digit value at the cursor position,
DECREASE
button to move cursor to next position to the right or the
INCREASE
button to move the cursor
to previous the position to the left. Decimal point can be used only once in the value field, to remove an unwanted
decimal point and change it to a number.
21. When the new value is entered, press the
DECREASE
button until the ‘SAVE AND RETURN’ item is selected
on the screen. (Pressing and holding the
DECREASE
button will have the same effect).
22. Press the
SELECT
button to save the new calibration data.
23. Dialog box will be displayed to confirm that the calibration was successfully completed. If the calibration fails,
it will need to be repeated.
24. Depressurize and disconnect an external meter from the calibration valve or calibration manifold.
25. Switch the calibration valve back to normal position, to direct foam flow into the water way.
Injector Foam Flow Calibration
Injector Foam Flow Meter measures the flow of foam concentrate injected the into water stream flowing through the
corresponding discharge. Calibration of the meter is done by comparing the volume of liquid measured by the master foam
flowmeter and one discharge from an injector. Calibration can be done using water instead of foam concentrate.
ATTENTION: Do not calibrate the Injector Foam Flow Meter, if the Master Foam Flow meter is not calibrated.
The Master Foam Meter must have an accurate calibration before the injectors can be calibrated.
This calibration must to be performed for all injectors' foam flowmeters in newly installed into the system. Injector
Foam Flowmeters can be calibrated in any order.
To perform this calibration the operator needs to:
1. Make sure all display modules show OFF state.
2. Select the discharge/foam injector to be calibrated and its corresponding display module.
3. Locate the foam calibration valve associated with an injector connected hose to direct flow back to the foam
supply or foam tank. FoamPro calibration kit P/N: 3430-0381 can be used in line with the hose to control back-
pressure during this calibration (
if the installation has a foam calibration manifold attached to an external hose
to the discharge side of manifold
).
4. Turn the calibration valve into the ‘Calibration’ position.
Содержание FoamPro Accumax II Fury