sTATus IndICATIon
The actuator status can be monitored in both Local and
Remote control modes.
Enter the VIEW mode to display current actuator Status.
Use the UP/DOWN Pushbuttons to scroll through currently
active alarms and status.
Fig 44.2 indicates that the actuator is selected for remote
operation and a Loss of signal demand alarm is currently
active.
See below for full list of possible Status & Alarm conditions.
Los dM - Los demand
The input demand signal is outside the minimum or maximum
range defined by the LOS LO and LOSS HI set parameters.
Los fb - Los feedback
Loss of internal position feedback. Actuator will lock in place.
sTL op - stall opening
Motor stalled in Open direction. Manually operate or drive the
actuator in the closed direction to clear the alarm.
sTL CL - stall Closing
Motor stalled in Closed direction. Manually operate or drive
the actuator in the open direction to clear the alarm.
oTQ op - over Torque opening
Max Torque exceeded in Open direction. Manually operate or
drive the actuator in the closed direction to clear the alarm.
oTh op - over Thrust opening
Max Thrust exceeded in Open direction. Manually operate or
drive the actuator in the closed direction to clear the alarm.
STATUS
REMOTE
LOS DM
REMOTE
VIEW
status Alarm Menu
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust or Torque
LOCREM
Local / Remote Control
MANJOG
Manual Jog
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CFG
Control Setup
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
BASIC
INFO
ACT STS
AMP STS
TEMP
SWR VER
CTR SETUP
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LOW
LOS HI
TORQ O
TORQ C
CL ACT
OP ACT
RELAYS
RLY1 CFG
RLY1 POS
RLY1 FRM
RLY2 CFG
RLY2 POS
RLY2 FRM
ACT CFG
ACT TYPE
ACT SIZE
ENCOD IN
ASRACT
SP RANGE
MIN CMD
MAX CMD
BSRACT
ST CUST
LD CUST
DEFAULTS
LD FACT
Los dM
Los fb
sTL op
sTL CL
oTQ op
oTh op
Fig. 44.2
Fig. 44.1
oTQ CL - over Torque Closing
Max Torque exceeded in Closed direction. Manually
operate or drive the actuator in the open direction to clear
the alarm.
oTh CL - over Thrust Closing
Max Thrust exceeded in Closed direction. Manually
operate or drive the actuator in the open direction to clear
the alarm.
oTQ CL
oTh CL