basic setup
2. seT ouTpuT ToRQue/ThRusT
If the Close Torque/Thrust value requires adjustment
press ENTER.
The actuator is now in EDIT Mode and the parameters
can be modified.
Use the UP/DOWN buttons until the correct Torque/Thrust
Value is displayed.
Press ENTER to save the changes. Visually confirm that the
parameter is saved.
Press CANCEL to return to previous menu.
Use UP/DOWN buttons until TORQ O is displayed.
Press ENTER to view the Open Torque or Thrust value.
Fig 32.5 shows the Open Torque value set to 100% of the
actuators rated value.
If the set value is correct press CANCEL to return back to
previous menu.
NOTE: The Output Torque or Thrust setting must be sufficient
to operate the valve under full working process conditions.
Press ENTER to change the Open Torque/Thrust value.
X
X
X
X
LOCAL
TORQ C
X
LOCAL
TO 100
%
VIEW
LOCAL
TC 400
%
EDIT
LOCAL
TC 700
%
EDIT
LOCAL
SAVED
VIEW
X