6. CTRCfg - Control setup
CTRLAL - Control Algorithm
Currently supports Open Loop control Only.
In dMp- Input damping
Time period over which the command input signal
is averaged.
Range is 0 to 10 Seconds.
Los To - Loss of signal Time out.
Loss of signal timeout can be set to between 0 to 5
seconds in 0.1 second increments.
Default is 0 seconds.
Los ACT - Loss of signal Action.
Action on loss of command signal.
Selections are:
CLs
-
Close
opn
- Open
spT
-
Stayput
pos
-
Run to Position
dIs
-
Disabled
Los Lo - Loss of signal Low
The threshold of command signal below the level classed as
‘LOST’. Adjustable between 3 to 4 mA. Default = 3.6 mA.
Los hI - Loss of signal high
The threshold of command signal above the level classed
as Lost or out of range. Adjustable between 20 to 21 mA.
Default = 20.4 mA.
Advanced Menu
ACT CFG
SPLT RANGE
CTRL SETUP
INFO
RELAYS
STALL TIME
CPT 20
CMD SRCE
CPT 4
ADVANCED
CTRCfg
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
CFG
Control Setup
INFO
ACT STS
AMP STS
TEMP
SWR VER
CTR SETUP
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LOW
LOS HI
RELAYS
RLY1 CFG
RLY1 POS
RLY1 FRM
RLY2 CFG
RLY2 POS
RLY2 FRM
ACT CFG
ACT TYPE
ACT SIZE
ENCOD IN
SP RANGE
MIN CMD
MAX CMD
BSRACT
ST CUST
LD CUST
DEFAULTS
LD FACT
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust Display or
Ouput Torque
LOCAL/REM
Local / Remote Operation
MANJOG
Manual Jog
TORQ/THRUST C
Close Torque/Thrust
TORQ/THRUST O
Open Torque/Thrust
CL ACT
Close Action
OP ACT
Open Action
BASIC
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
ASRACT
BSRPOS
CTRCfg - Control setup
CRTLAL - Control Algorithm
In dMp - Input damping
Los To - Loss of signal Time out
Los ACT - Loss of signal Action
Los Low - Loss of signal Low
Los hI - Loss of signal high