52
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
CTR CFG
Control Configuration
AdvAnCed seTTIngs
CpT 4 - Current pos
Transmitter - Zero/4 ma
CpT 20 - Current pos
Transmitter - spAn (20 mA)
sTL To - sTALL TIMe
CMdsRC - CoMMAnd souRCe
Info
CTRCfg - ConTRoL
ConfIguRATIon
ReLAys - ReLAy
ConfIguRATIon
spL TRg - spLIT RAnge
ACTCfg - ACTuAToR
ConfIguRATIon
AdvAnCed Menu
Parameters can only be changed with actuator selected to
Local Operation Mode only.
Press UP/DOWN pushbuttons until ADVANC menu is
displayed. Press Enter to gain access to the Advanced Menu
parameters.
Use the UP/DOWN pushbuttons to scroll through the
Advanced menu Parameters. Once the correct parameter is
displayed and you wish to modify the parameter press ‘Enter’
to go to Edit Mode .
Use the UP/DOWN pushbuttons to modify the parameter
setting. Press Enter again to store selection. The display will
confirm that your selection has been SAVED.
press Cancel to return to previous menu.
1. CpT 4 Current position Transmitter - Zero Adjustment
The CPT is factory set but can be adjusted if necessary.
Calibrate 4 mA Transmitter output.
Connect MA source and meter.
Enter Edit mode and use the UP/Down pushbuttons to adjust
the 4 mA (ZERO) output.
2. CpT 20 Current position Transmitter - span Adjustment
The CPT is factory set but can be adjusted if necessary.
Connect MA source and meter.
Enter Edit mode and use the UP/Down pushbuttons to adjust
the 20 mA SPAN output.
3. sTL To - sTALL TIMe
Motor stall time adjustable between 1 to 100 seconds.
DEFAULT is 2 Seconds.
4. CMd sRCe - CoMMAnd souRCe
Select between Analogue, Digital or Bus Remote commands.
5. Info
Select between Actuator Starts, Amplifier Starts, Temperature
and Software Version.
Advanced Menu
AdvAnCed
CpT4
CpT20
sTL To
CMd sRCe
Info
STALL TIME
CPT 20
CMD SRCE
CPT 4
INFO
SPLT RANGE
RELAYS
ACT CFG
ADVANCED
CFG
Control Setup
INFO
ACT STS
AMP STS
TEMP
SWR VER
CTR SETUP
CTRLAL
IN DMP
LOS TO
LOS ACT
LOS LOW
LOS HI
RELAYS
RLY1 CFG
RLY1 POS
RLY1 FRM
RLY2 CFG
RLY2 POS
RLY2 FRM
ACT CFG
ACT TYPE
ACT SIZE
ENCOD IN
SP RANGE
MIN CMD
MAX CMD
BSRACT
ST CUST
LD CUST
DEFAULTS
LD FACT
POSIT
Position
SET PT
Setpoint
THRUST or TORQUE
Thrust Display or
Ouput Torque
LOCAL/REM
Local / Remote Operation
MANJOG
Manual Jog
TORQ/THRUST C
Close Torque/Thrust
TORQ/THRUST O
Open Torque/Thrust
CL ACT
Close Action
OP ACT
Open Action
BASIC
CL LIM
Close Limit (zero)
OP LIM
Open Limit (span)
CMD4
Field Command Signal4
CMD20
Field Command Signal20
DBAND
Deadband
FLTHST
Fault History Access
ADVANC
Advanced Menu
DEFLTS
Default Menu Access
STATUS
ASRACT
BSRPOS
InfoRMATIon
ACT sTs - ACCounT sTARTs
AMp-sTs - AMpLIfIeR sTARTs
TeMp - TeMpeRATuRe
swR veR - sofTwARe veRsIon