70
Reference Manual
00809-0200-4840, Rev BA
December 2014
Section 4: Configuration
Field Communicator or AMS
To view or change the threshold size:
1.
From the
Home
screen, select
2: Configure
.
2.
Select
2: Manual Setup
.
3.
Select
7: Advanced Processing
.
4.
Select
2: Threshold
.
5.
Select
7: Threshold 1 Size P048
.
6.
Input a new value, and then select “
ENTER
” to save it.
7.
Press “
SEND
” to update the transmitter.
Rosemount 3490 Series Control Unit
To view or change the threshold size:
1.
From the
Main Menu
screen, select
SETUP
.
2.
Select the transmitter (e.g. “
Tx1: 3107
”).
3.
Select
ENGINEERING
.
4.
Select
ADVANCED
.
5.
Select
Thresh 1 Size
.
6.
Follow the on-screen instructions to edit and save the new setting.
(Press the
Enter
(
) key if prompted to change the mode to “off-line”).
7.
Select “
Quit
” to exit to the previous menu.
Threshold 1 Size P048
4.0 %
4.0
ESC
DEL
ENTER
HELP
w
s
q
a
z
Lock
Shift
@ &
á ü
x
e
d
c
r
f
v
t
g
b
y
h
n
u
j
m
*
-
+
/
.
0
7
4
1
8
5
2
9
6
3
i
k
o
l
FN
(Field Communicator Screen)
Thresh 1 Size P048
4.0%
Esc=Quit =Edit
(Rosemount 3491 Screen)
Содержание 3107
Страница 2: ......
Страница 4: ...Reference Manual 00809 0200 4840 Rev BA Title Page December 2014 ...
Страница 10: ...TOC vi Reference Manual 00809 0200 4840 Rev BA Table of Contents December 2014 Table of Contents ...
Страница 16: ...6 Reference Manual 00809 0200 4840 Rev BA Section 2 Transmitter Overview December 2014 ...
Страница 90: ...80 Reference Manual 00809 0200 4840 Rev BA Section 4 Configuration December 2014 Section 4 Configuration ...
Страница 144: ...134 Reference Manual 00809 0200 4840 Rev BA Appendix D Field Communicator December 2014 Appendix D Field Communicator ...
Страница 145: ......
Страница 146: ......
Страница 147: ......