Section 4: Configuration
Tank Shape/NLP (P011) = “Horizontal Cyl Flat”
This Horizontal Cylinder With Flat Ends setting is applicable when volume measurements are
needed from a horizontally-oriented cylindrical tank with a constant diameter (see
for a cross-sectional view).
The volume is calculated from the live level measurement, the full volume of an ideal cylindrical
tank, and the diameter of that tank.
Setting-up Procedure for “
Horizontal Cyl Flat
”:
1.
Use the
Tank Shape/NLP
(
P011
) parameter to select the option “
Horizontal Cyl Flat
”.
2.
Enter the full volume into the
PV Scale Factor
parameter (
).
3.
Enter the tank diameter into the
Profile Height / Power Factor
parameter (
Tank Shape/NLP (P011) = “Spherical”
This setting is applicable when volume measurements are needed from a spherical tank with a
constant diameter (see
for a cross-sectional view).
The volume is calculated from the liquid level measurement and the full volume of the ideal
spherical tank.
Setting-up Procedure for “
Spherical
”:
1.
Use the
Tank Shape/NLP
(
P011
) parameter to select “
Spherical
”.
2.
Enter the full volume into the
PV Scale Factor
parameter (
).
3.
Enter the tank diameter into the
Profile Height / Power Factor
parameter (
Содержание 3107
Страница 2: ......
Страница 4: ...Reference Manual 00809 0200 4840 Rev BA Title Page December 2014 ...
Страница 10: ...TOC vi Reference Manual 00809 0200 4840 Rev BA Table of Contents December 2014 Table of Contents ...
Страница 16: ...6 Reference Manual 00809 0200 4840 Rev BA Section 2 Transmitter Overview December 2014 ...
Страница 90: ...80 Reference Manual 00809 0200 4840 Rev BA Section 4 Configuration December 2014 Section 4 Configuration ...
Страница 144: ...134 Reference Manual 00809 0200 4840 Rev BA Appendix D Field Communicator December 2014 Appendix D Field Communicator ...
Страница 145: ......
Страница 146: ......
Страница 147: ......