47
Reference Manual
00809-0200-4840, Rev BA
December 2014
Section 4: Configuration
Figure 4-5. Cylindrical or spherical tank cross-section
Tank Shape/NLP (P011) = “Horizontal Cyl Dome”
This Horizontal Cylinder With Domed Ends setting is applicable when volume measurements are
needed from a horizontally-oriented cylindrical tank with a constant diameter (see
for a cross-sectional view).
The volume is calculated from the live level measurement, the full volume of an ideal cylindrical
tank, and the diameter of that tank.
Setting-up Procedure for “
Horizontal Cyl Dome
”:
1.
Use the
Tank Shape/NLP
(
P011
) parameter to select the option “
Horizontal Cyl
Dome
”.
2.
Enter the full volume into the
PV Scale Factor
parameter (
).
3.
Enter the tank diameter into the
Profile Height / Power Factor
parameter (
P013 = Full Volume of Ideal Cylindrical or Spherical Tank of Constant Diameter P014
4–20mA/HART
Rosemount
3107 or 3108
Rosemount
3490 Series
Pr
of
ile
He
igh
t (
P0
14
)
Bo
tt
om
R
e
fe
re
nc
e
(P01
0)
Содержание 3107
Страница 2: ......
Страница 4: ...Reference Manual 00809 0200 4840 Rev BA Title Page December 2014 ...
Страница 10: ...TOC vi Reference Manual 00809 0200 4840 Rev BA Table of Contents December 2014 Table of Contents ...
Страница 16: ...6 Reference Manual 00809 0200 4840 Rev BA Section 2 Transmitter Overview December 2014 ...
Страница 90: ...80 Reference Manual 00809 0200 4840 Rev BA Section 4 Configuration December 2014 Section 4 Configuration ...
Страница 144: ...134 Reference Manual 00809 0200 4840 Rev BA Appendix D Field Communicator December 2014 Appendix D Field Communicator ...
Страница 145: ......
Страница 146: ......
Страница 147: ......