Table 13 - Resistive Brake Module
Noise Reduction Guidelines for Drive Accessories
Refer to this section when mounting an AC (EMC) line filter or external shunt
module for guidelines designed to reduce system failures caused by excessive
electrical noise.
AC Line Filters
Observe these guidelines when mounting your AC (EMC) line filter (refer to the
figure on
for an example):
•
Mount the AC line filter on the same panel as the Kinetix 6000 drive and
as close to the power rail as possible.
•
Good HF bonding to the panel is critical. For painted panels, refer to the
examples on
•
Segregate input and output wiring as far as possible.
Wire/Cable
Connections
Zone
Method
Very
Dirty
Dirty
Clean
Ferrite
Sleeve
Shielded
Cable
Resistive brake module coil power
TB3-6 and TB3-7
X
Resistive brake module I/O
TB1-1…TB1-5
and TB3-8
X
Resistive brake module
drive and motor power
TB1 and TB2
X
X
230V power
TB4
X
IMPORTANT
CE test certification applies only to AC line filter and single power rail.
Sharing a line filter with multiple power rails may perform satisfactorily,
but the user takes legal responsibility.
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......