Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
257
Changing the Default IDN Parameter Values
Appendix E
Write the New IDN Parameter Value
Follow these steps to write the new IDN parameter value.
1.
Configure a Message Configuration (MSG) instruction to write the IDN
parameter value required for your application.
In this example, the Message Configuration (MSG) instruction is set to
write the additional bus capacitance of your leader IAM power module.
a. From the Message Type pull-down menu, choose SERCOS IDN Write.
b. From the Identification Number pull-down menus, choose P-0-99.
2.
Click New Tag.
3.
The New Tag dialog box opens.
4.
Type the name of your Source tag.
In this example, the tag name is Write_Value.
5.
Click OK.
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......