Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
151
Configure and Start Up the Kinetix 6000 Drive System
Chapter
6
3.
Type values for Travel Limit and Speed.
In this example, Travel Limit = 5 and Speed = 10. The actual value of
programmed units depend on your application.
4.
From the Direction pull-down menu, choose a setting.
Forward Uni-directional is default.
5.
Check Tune boxes as appropriate for your application.
6.
Apply Hardware Enable Input signal (IOD-2) for the axis you are tuning.
7.
Click Start Tuning to auto-tune your axis.
The Online Command - Tune Servo dialog box opens. When the test
completes, the Command Status changes from Executing to Command
Complete.
8.
Click OK.
The Tune Bandwidth dialog box opens.
Actual bandwidth values (Hz) depend on your application and may
require adjustment once motor and load are connected.
9.
Record your bandwidth data for future reference.
10.
Click OK.
ATTENTION:
To avoid personal injury or damage to equipment,
apply 24V ENABLE signal (IOD-2) only to the axis you are tuning.
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......