64
Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 4
Kinetix 6000 Connector Data
Figure 27 - Enable, Home, and Overtravel Digital Input Circuits
(1) 24V DC source (range) = 21.6V - 26.4V (supplied by drive, not to exceed 250 mA total).
Maximum current input = 10 mA.
Figure 28 - Registration Digital Input Circuits
SERCOS Communication Specifications
The Rx and Tx SERCOS connectors are provided on the Kinetix 6000 IAM and
AM module for communication with the Logix controller.
3k
Ω
0.1
μ
F
511
Ω
VCC
CTRL_INPUT
INPUT
IO_COM
I/O SUPPLY
IOD-1, -4, -7, -10
IOD-2, -5, -8, -11
IOD-3, -6, -9, -12
1k
Ω
Kinetix 6000
IAM/AM Module
Customer-supplied Input Device
24V DC
(1)
3k
Ω
511
Ω
VCC
REG_INPUT
INPUT
IO_COM
HCPL-0631
I/O SUPPLY
+24V DC
IOD-13, -16
IOD-14, -17
IOD-15, -18
0.001
μ
F
1k
Ω
Kinetix 6000
IAM/AM Module
Customer-supplied Registration
Input Device
Attribute
Value
Data rates
4 and 8 Mbps, selectable via DIP switch
Light intensity
Low power or high power, selectable via DIP switch
Cyclic update period
500 µs, min
Node addresses
01…99
(1)
(1) Node address assignments begin with the IAM module. Node addresses for additional axes on the same power
rail are assigned by incrementing from left to right (starting with the IAM module address).
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......