248
Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Appendix D
DC Common Bus Applications
Common Bus Capacitance
Example
In this example, the sum of the leader IAM power rail modules capacitance
(6530 μF) and the follower IAM power rail modules capacitance (5280 μF)
equals 11,810 μF total bus capacitance.
The sum of the follower IAM module power rail equals 5280 μF additional bus
capacitance.
Figure 113 - Calculating Common Bus Capacitance
MAIN VAC
LIM Module
(optional
component)
Three-phase
Input Power
Kinetix 6000 (230V)
Leader IAM Module
AC Line
Filter
Kinetix 6000 (230V)
Follower IAM Module
5280 µF Additional Bus Capacitance
11,810 µF Total Bus Capacitance
DC Common Bus
2094-PRF Slot-filler Module N/A
2094-BSP2 Shunt Module, 470 µF
2094-AM02-
x
AM Module, 780 µF
2094-AM03-
x
AM Module, 1320 µF
2094-AM03-
x
AM Module, 1320 µF
2094-AC16-M03-
x
IAM Converter, 1320 µF
2094-AC16-M03-
x
IAM Inverter, 1320 µF
2094-PRF Slot-filler Module, N/A
2094-AM03-
x
AM Module, 1320 µF
2094-AM03-
x
AM Module, 1320 µF
2094-AC16-M03-
x
IAM Converter, 1320 µF
2094-AC16-M03-
x
IAM Inverter, 1320 µF
Содержание Allen-Bradley 2094-BC01-M01-S
Страница 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Страница 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Страница 126: ...126 Rockwell Automation Publication 2094 UM001D EN P May 2010 Chapter 5 Connecting the Kinetix 6000 Drive System Notes...
Страница 228: ...228 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix B Interconnect Diagrams Notes...
Страница 270: ...270 Rockwell Automation Publication 2094 UM001D EN P May 2010 Appendix F RBM Module Interconnect Diagrams Notes...
Страница 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Страница 279: ......