88
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 2 Installation Instructions
The module also monitors the input data paths and can detect faults within
each input channel. A visual indication of the module status and individual
channel status is provided by an array of front panel indicators and can be
connected to tags within the Studio 5000 Logix Designer® application.
The termination assemblies can accept one or two input modules. Each
termination assembly provides passive signal load termination and over-
voltage protection for each input channel. The system provides flexible input
connectivity by mating specific termination assemblies with the relevant
number of input modules.
Field Loop Circuits for Analog Inputs
These circuits can be used for simplex and duplex configurations of analog
input modules. Fit a suitably rated fuse,“F1” in each circuit to help protect the
field wiring, terminal block and 4mA -20mA current generator.
This field loop connection method is used for two-wire field devices.
Figure 46 - Two-wire Analog Input Field Loop Circuit
This field loop connection is used for three-wire analog field devices. Fit a
suitably rated fuse, “F2” in each circuit to help protect the field wiring, terminal
block and 4mA -20mA current generator.
Shield
Required
Terminal
Blocks
OV
Termination
Assembly
+24V DC
4…20 mA
2-Wire Analog Input
50 mA
120Ω
32116 M
F1
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...