Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
231
Chapter 8 Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules
3. Create a reset tag by using the default data type and Read/Write External
Access.
The tag can be controller- or program-scoped.
4. Choose the module configuration tag.
If you have multiple modules, be sure to choose the configuration tag for
the appropriate module.