260
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Appendix B 1715-IB16D Digital Input Module Diagnostics
The same is true with an ‘off’ condition. The module reports an ‘off’ condition
anytime the voltage is below ~5.5V, but does not report a wire off, because it
has to go below 0V to do so.
Custom Diagnostics Configuration
For custom diagnostics, you calculate and enter the threshold values.
To calculate the desired values, see
Calculate Threshold and Resistor Values on
Once calculated, follow these steps to enter the settings.
1. From the Diagnostics pull-down menu, choose Custom.
2. Click Edit from the Custom Thresholds column.
3. Enter the desired value ranges into the Threshold dialog boxes.
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...