262
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Appendix B 1715-IB16D Digital Input Module Diagnostics
Figure 79 - Open Switch/Off Condition
If 5.1V is present, we know that the switch is in the off position. We can enter a
range into the threshold that lets 5.1V to be an off condition. We used 3.0 …6.5V
as the range. So, if the voltage drops below 3.0V, it is considered a wire off. If it
goes above 6.5V, it is considered indeterminate.
Shield
(if used)
Terminal
Blocks
OV
20
Ω
100
Ω
50 mA
4.99k
Ω
Termination
Assembly
+24V DC
R1
R2
45678
User-calculated Voltage
5.1 K
SW1
3.9 k
15 k
45680
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...