Appendix F I/O Tag Definitions
FieldPowerVoltage2
DINT
Reports the voltage from the field power supply for the specified module and field power input.
Accuracy is ± 500mV
Ch
AB_1715_ChStatusStruc:I:0[8]
Current / Voltage
Status Array
Each element of the array
comprises
Current: REAL
Reports the current for the channel in
milliamps and with an accuracy of ± 2 mA
and ± 10% of measurement
Voltage: REAL
Reports the channel voltage at the output
terminals in units of millivolts and with an
accuracy of ± 500 mV (The voltage element
cannot report values below 0 mV
Table 68 - 8-channel Digital Output, Duplex, Input
Tag Name
Data Type
Definition
Fault
DINT, Binary
Module fault bit:
0 when one module is present and reporting valid data, OxFFF_FFFF
when no modules are present, no Logix connection exists, or reported
data is invalid.
ReadBack
SINT
Output channel read-back state, one bit per channel for channels 0…7:
0 = Off/de-energized
1 = On/energized
Status
DINT, bit-field
Redundancy and power status:
Bit
Name
Description
0
ModAFault
0 = Good
1 = Fault or module not present
1
ModBFault
0 = Good
1 = Fault or module not present
8
GroupFault
0 = Good
1 = Any channel or module faulted/failed
9
ModAGroupFault
0 = Good
1 = Any channel or module A faulted/
failed
10
ModBGroupFault
0 = Good
1 = Any channel or Module B faulted/
failed
PtFault
SINT
Channel fault status; one bit per channel for channels 0 …7:
0 = Normal
1 = Pint is faulted/failed
NoLoad
SINT
No Load diagnostic status, one bit per channel for channels 0…7:
0 = Normal
1 = Indicates no load detected
ShortCircuit
SINT
Short Circuit diagnostic status, one bit per channel for 0…7 channels:
0 = Normal
1 = Indicates short circuit detected
GroupFieldPowerCurrent
DINT
Reports the total current that all the active digital output modules in a group are drawing from the
field power supply. Accuracy is ± 10%.
ModAFieldPowerVoltage1
DINT
Reports the voltage from the field power supply for the specified module and field power input.
Accuracy is ± 500mV
ModAFieldPowerVoltage2
DINT
Reports the voltage from the field power supply for the specified module and field power input.
Accuracy is ± 500mV
ModBFieldPowerVoltage1
DINT
Reports the voltage from the field power supply for the specified module and field power input.
Accuracy is ± 500mV
Table 67 - 8-channel Digital Output, Simplex, Input
Tag Name
Data Type
Definition
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...