186
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 6 Configure the Redundant I/O System
4. Click Change.
5. Enter the parameters, see
.
6. Click OK.
7. Click the Connection tab, see
.
8. Click the Module Info A tab, see
.
9. Click the Module Info B tab, see
10. Click the Configuration tab.
The Configuration tab appears.
11. Click the Fault/Program Action tab.
The Fault/Program Action tab appears.
Table 32 - Configuration Parameters for Digital Output Module in Duplex Mode
Parameters
Description
Point
Click the point number to configure parameters for the specified point (0…7).
No Load Detection
By default, the header checkbox is selected and all points (0…7) are selected. If the header
checkbox is cleared, all points (0…7) are cleared.
To specify no load detection for a specific point, check the checkbox in the appropriate row
for that point.
To clear no load detection for a specific point, clear the checkbox in the appropriate row for
that point.
Latch No Load Diagnostics
Choose if load fault alarms are latched until reset (including Open Wire Detection and Short
Circuit detection). By default, the header checkbox is selected and all points (0…7) are
selected. If the header checkbox is cleared, all points (0…7) are cleared.
To select load fault alarms are latched until reset for a specific point, check the checkbox in
the appropriate row for that point.
To clear load fault alarms are latched until reset for a specific point, clear the checkbox in
the appropriate row for that point.
Reset Latched Diagnostics
Click Reset to reset the diagnostic latch service.
When online and in Program mode, Remote Program mode, Run mode, the Reset button is
enabled for a point. When offline, the Reset button is dimmed for a point.
Reset Fuse
Click Reset to reset the fuse reset short/overload service.
When online and in Program mode, Remote Program mode, Run mode, the Reset button is
enabled for a point. When offline, the Reset button is dimmed for all points.
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...