Chapter 4 Digital I/O Operation
Tag
Description
Simplex Digital Output Module Tags Include
Fault
DINT Fault (Radix = Binary) - 0 at least one module present, data good
- FFFFFFFF No Logix connection, data bad, all additional tags are not valid
ReadBack
SINT (Radix = Binary)
- 1 bit readback per point 0…7
GroupFault
BOOL
- 1 if any point on the module is faulted/failed
PtFault
SINT (Radix = Binary)
- 1 bit per point 0…7; 1 if point is faulted/failed
NoLoad
SINT (Radix = Binary)
- 1 bit per point 0…7; 1 indicates no load
ShortCircuit
SINT (Radix = Binary)
- 1 bit per point 0…7; 1 indicates short circuit
Duplex Digital Output Module Tags Include
Fault
DINT Fault (Radix = Binary) - 0 at least one module present
- FFFFFFFF No Logix connection, all additional tags are not valid
ReadBack
SINT (Radix = Binary)
- 1 bit readback per point 0…7
ModAFault
BOOL
- 0 Good, 1 fault or module not present
ModBFault
BOOL
- 0 Good, 1 fault or module not present
GroupFault
BOOL
- 1 if any point on either module is faulted/failed
ModAGroupFault
BOOL
- 1 if any point on Module A is faulted/failed
ModBGroupFault
BOOL
- 1 if any point on Module B is faulted/failed
PtFault
INT (Radix = Binary)
- 1 bit per point 0…15; 1 if point is faulted/failed on both modules
ModAPtFault
INT (Radix = Binary)
- 1 bit per Channel 0…15; 1 if channel has failed on module A
ModBPtFault
INT (Radix = Binary)
- 1 bit per Channel 0…15; 1 if channel has failed on module B
NoLoad
SINT (Radix = Binary)
- 1 bit per point 0…7; 1 indicates no load
ShortCircuit
SINT (Radix = Binary)
- 1 bit per point 0…7; 1 indicates short circuit
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...