35
Parameters Menu Commissioning
Commissioning menu
Description
Parameter
Selection
Set
Time and date
1
Hours / Minutes
2
Month / Day
3
Year
Control unit
20
Language
Time program heating
circuit 1
500-516
Preselection, Periods
Time program heating
circuit 2
520-536
Preselection, Periods
Time program 3 / HC
540-556
Preselection, Periods
Time program 4/ACS
560-576
Preselection, Periods
Time program 5
600-616
Preselection, Periods
Holiday CR 1
641-648
Periods, Start-End
Holiday CR 2
651-658
Periods, Start-End
Holiday CR 3
661-668
Periods, Start-End
Heating circuit 1
710
Comfort
20 °C
712
Reduced
16 °C
714
Anti-freeze protection
4 °C
720
Climate curve
1.50
730
Summer / winter limit value 18 °C
740
Supply sepoint min
40 °C
741
Supply sepoint max
80 °C
Heating circuit 2
1010
Comfort
20 °C
1012
Reduced
16 °C
1014
Anti-freeze protection
4 °C
1020
Climate curve
1.50
1030
Summer / winter limit value 18 °C
1040
Supply sepoint min
40 °C
1041
Supply sepoint max
80 °C
Heating circuit 3
1313
Comfort
20 °C
1312
Reduced
16 °C
1314
Anti-freeze protection
4 °C
1320
Climate curve
1.50
1330
Summer / winter limit value 18 °C
1340
Supply sepoint min
40 °C
1341
Supply sepoint max
80 °C
Domestic Hot Water
(DHW)
1610
Nominal setpoint
55°C
1620
Consent 24 hours / day
24 hours / day
1630
Load priority
no one
Boiler
2214
Manual working
temperature
60°C
Configuration
5700
Preselection
-
5710
Circuit activation HC 1
On
5715
Circuit activation HC 2
Off
5721
Circuit activation HC 3
Off
5730
DHW sensor type
Sensor
5731
DHW control element
Load pump
5733
DHW pump post circulation
time
0 seconds
5890
QX1 relay
Boiler pump
5891
QX2 relay
To be set
5892
QX3 relay
To be set
Configuration
5930
Input probe BX1
Common flow
probe
5931
Input probe BX2
To be set
5932
Input probe BX3
Smoke
temperature
probe
5970
Input function H4
To be set
5971
Contact logic H4
NA
5973
Frequency value 1
To be set
5974
Value 1 H4
To be set
5975
Frequency value 2
To be set
5976
Value 2 H4
To be set
5977
Input function H5
To be set
5978
Contact logic H5
NA
6008
Input function H6
To be set
6009
Contact logic H6
NA
6011
Input function H7
To be set
6012
Contact logic H7
NA
6100
Temp adjustment external
0 ° C
6200
Save all changes
LPB (cascade
management)
6600
Device address
1
6640
Watch mode
Master
Fault
6705
Diagnostic code
Error diagnostics
Operation Maintenance
Service
7130
Chimney sweep function
Off
7131
Burner power
Max
7140
Manual control
Off
7146
De-aeration function
Off
Test input / output
7700
Relay test
No testing
7730-7823
Boiler probe
7830-7835
External module probe
State
8000
Heating circuit status HC1
8001
Heating circuit status HC2
8002
Heating circuit status HC3
8003
DHW heating circuit status
8005
Boiler status
8007
Solar circuit
8009
Burner
8011
Pool status
Diagnostic parameters
8310
Boiler flow temp
8311
Boiler setpoint flow temp
8312
Boiler switching point
8314
Boiler return temp
8316
Smoke temperature
8318
Maximum smoke temp.
8321
Primary exchanger temp
8323
Number of fan revolutions
8326
Burner modulation
8327
Water pressure
8329
Ionization current
Parameters Menu Commissioning
Requirements and conditions