The display shows “ ” to indicate the presence of a flame.
18/05/2013
12:17
MENU
INFO
SET
107
°F
FRI
PLANT
HOT WATER TEMPERATURE
STATE
18.85 psi
MENU
STATE
SET
INFO
PLANT
HOT WATER TEMPERATURE
FRI
The boiler will run until the selected temperature is reached,
afterwards it will be in “standby” again, keeping the outlet
temperature displayed.
If faults arise in ignition or operation, the boiler performs a
“SAFETY STOP”: the triangle signal fault will flash on the front
control. To identify the fault codes and to reset the boiler, see
section “11.22 Lights and faults”.
E010
FLAME LOCKOUT
PRESS OK RESET
FLAME LOCKOUT
PRESS OK/ENTER TO RESET
11.18
Reset function
In the event of a lockout, it is possible to try and reset the
normal operation of the appliance by pressing the “ENTER”
button on the front control when the fault message is displayed
for resetting the error in progress.
9
If the release attempts do not restart the boiler, contact the
local Technical Assistance Centre.
11.19
Checks during and after the first
commissioning
After start-up check that the boiler carries out the start-up
procedures and subsequent shut-down properly.
Check the domestic hot water operation by opening a hot water
tap in Indirect tank or HEATING AND HOT WATER mode.
Check the full stoppage of the boiler by turning off the system’s
main power switch.
After a couple of minutes of continuous operation with the
boiler mode selector to HOT WATER ONLY mode and by keeping
the domestic hot water tap open, it will be possible to carry out
a combustion check.
BOILER
OFF
HOT WATER ONLY
HEATING AND HOT WATER
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
11.20
Converting the boiler gas type
The Family PRO boiler is factory supplied to use natural gas (gas
A). The boiler can use also LP (gas E) by setting the parameter.
9
WARNING
: The boiler may only be converted by qualified
technician. Failure to comply may result in substantial
property damage, severe personal injury or death.
To convert the boiler to LPG (gas E) proceed as follows:
− access the technical parameters as explained in the section
“11.6 Access to the technical parameters”
− set the INSTALLER password “018”
9
WARNING
: The parameters accessed by using this parameter
should only be adjusted by a qualified service technician.
Failure to comply may result in substantial property damage,
severe personal injury or death.
− select COMBUSTION MONITORING with the “up” and “down”
buttons, confirming the selection by pressing the “ENTER”
button
-
AIR PURGING CYCLE
PARAMETERS
EXHAUST PROBE RESET
ALARM HISTORY
COMBUSTION CHECK
SERVICE
TECHNICAL
ERROR HISTORY
EXHAUST PROBE RESET
AIR PURGING CYCLE
PARAMETERS
COMBUSTION MONITORING
TECHNICAL
SERVICE
select GAS TYPE
COMBUSTION CHECK
COMBUSTION OFFSET
BOILER TYPE
GAS TYPE
SERVICE
BOILER TYPE
COMBUSTION OFFSET
GAS TYPE
COMBUSTION MONITORING
SERVICE
− select LPG
GAS TYPE
LPG
NG
SERVICE
NATURAL GAS
LPG
GAS TYPE
SERVICE
The boiler DOES NOT require additional adjustments.
9
WARNING
: After conversion apply the new rating plate
supplied with the boiler. Failure to do so may result in
substantial property damage, severe personal injury or
death.
GAS
LABEL
THIS GAS BOILER IS CONVERTED FOR USE WITH
LP GAS
SUPPLY PRESSURE 11 in w.c./27.4 mbar
CETTE CHAUDIERE A GAZ EST REGLEE POUR
FONCTIONNER AU
LP GAZ
PRESSION
D’ALIMENTATION DU GAZ 11 in w.c./27.4 mbar
11.21
Combustion analysis
To carry out the combustion analysis, proceed as follows:
- power the boiler electrically by turning the main power
switch to “ON”
- set the status of the boiler to OFF