17
9
WARNING
: The space must be provided with combustion/
ventilation air openings correctly sized for all other
appliances located in the same space as the Family PRO
boiler. The boiler front cover must be securely fastened
to the boiler to prevent the boiler from drawing air from
inside the boiler room in a sealed combustion application.
This is particularly important if the boiler is located in the
same room as other appliances. Failure to comply with the
above
WARNING
s could result in severe personal injury,
death or substantial property damage.
6.4
Exhaust vent and intake air vent
Family PRO are certified to the ANSI Z21.13-2017
CSA 4.9-2017 –
Gas-Fired low pressure steam and hot water boilers. Direct vent,
Category IV (likely to condense in the vent) appliances.
NOTICE
: To prevent combustion air contamination when
considering the exhaust vent and intake air vent termination,
intake and exhaust may be vented vertically through the roof or
out a side wall.
The intake and exhaust venting methods are detailed in the
General venting Section. Do not attempt to install the Family PRO
Boiler using any other means. Be sure to locate the boiler such
that the air intake and exhaust vent piping can be routed through
the building and properly terminated. The air intake and exhaust
vent piping lengths, routing and termination method must all
comply with the methods and limits given within the Venting
section.
6.5
Prevent combustion air contamination
Install intake air piping for the Family PRO as described in the
Venting section. Do not terminate exhaust in locations that can
allow for contamination of the intake air.
9
WARNING
: You must pipe outside air to the boiler air intake for
sealed combustion operation. Ensure that the intake air will
not contain any of the contaminants below. Contaminated
air will damage the boiler, resulting in possible severe
personal injury, death or substantial property damage. For
example, do not pipe the intake air vent near a swimming
pool. Also avoid areas subject to exhaust fumes from laundry
facilities. These areas may contain contaminants.
6.6
When removing an existing boiler from an
existing common vent system
Do not install the Family PRO boiler into a common vent with any
other appliance. This will cause flue gas spillage or appliance
malfunction, resulting in possible severe personal injury, death
or substantial property damage.
9
WARNING
: Failure to follow all instructions can result in
flue gas spillage and carbon monoxide emissions, causing
severe personal injury or death.
When an existing boiler is removed from a common venting
system, the common venting system is likely to be too large for
proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected
to the common venting system placed in operation, while the
other appliances remaining connected to the common venting
system are not in operation.
A
Seal any unused openings in the common venting system.
B
Visually inspect the venting system for proper size and
horizontal pitch and to determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
C
Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances
remaining connected to the common venting system are
located and other spaces of the building, so long as it is
practical to do so. Turn on clothes dryers and any appliance not
connected to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer exhaust
fan. Close fireplace dampers.
D
Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so the appliance will
operate continuously.
E
Test for spillage at the draft hood relief opening after 5 minutes
of main burner operation. Use the flame of a match or candle, or
smoke from a cigarette, cigar or pipe.
F
After it has been determined that each boiler remaining connected
to the common venting system properly vents when tested as
outlined above, return doors, windows, exhaust fans, fireplace
dampers and any other gas burning boiler to their previous
condition of use.
G
Any improper operation of the common venting system should
be corrected so the installation conforms with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edition. Correct by
resizing to approach the minimum size as determined using the
appropriate tables in ANSI Z223.1/NFPA 54 of that code. Canadian
installations must comply with CAN/CSA B149.1 Installation Code.
9
WARNING
: Verify proper operation after servicing.
6.7 Prepare the Family PRO
9
CAUTION
: Cold weather handling — If boiler has been stored
in a very cold location (below 0°F (-18°C)) before installation,
handle with care until the plastic components come to
room temperature.
7 INSTALLATION
7.1
Wall mounting information
Family PRO comes with a template, which allows you to easily
mark the location of the screws for the mounting bracket and
the location of the flue gas pipe on the wall.
The gas connection must be made on site, a 3/4” gas cock is
supplied with the boiler.
9
WARNING
: This boiler is heavy and awkward to lift. It is
recommended and safer to install the boiler with two people.
Use
CAUTION
as to not drop the boiler which could cause
personal injury. Verify that the boiler is securely mounted
before leaving the boiler unsupervised.
The wall must be vertically plumb and capable of carrying the
weight of the Family PRO and its related components.
9
CAUTION
: If the Family PRO is not vertically plumb, improper
and unsatisfactory operation may occur. This will cause
excessive condensation build-up resulting in unnecessary
maintenance and nuisance fault codes.
NOTICE
: The mounting bracket is shown for installation of the
Family PRO 42 and IS boiler.
7.1.1
Placing the wall-mounted Family PRO
boiler
Family PRO boilers are wall mounted. Use only the Family PRO 42 and
IS boiler wall mounting instructions included in the box.
9
WARNING
: The wall must be capable of carrying the weight
of the boiler and its related components. The shipping
weights of the boiler are approximately:
Family PRO 42 combi = 97 lbs (44 kg)
Family PRO 42 heating only = 93 ibs (42 kg)
Failure to comply with above could result in severe personal
injury, death or substantial property damage.