23

ENGLISH

EN

CONFIRM OR DELETE SELECTION

CONFIRM

CANCEL

THE PARAMETER WILL BE 

CHANGED

58,0

°C

HOT WATER

SET

9.3 

Cooling (available if heat pump enabled for cooling is installed)

Press the “

+

” and “

-

” keys

 to change the cooling setpoint and then confirm

. If the thermoregulation 

in cooling is activated, the flow temperature value is automatically chosen by the system, which 

rapidly adjusts the room temperature according to the variations in the external temperature. 

If you want to change the temperature value, increasing or decreasing it compared to that 

automatically calculated by the electronic board, you can change the COOLING setpoint by 

choosing the desired comfort level (-5 ÷ +5) within the range. Then you are asked to confirm 

the setpoint setting: select ENTER or BACK using “

+

” and “

-

”, validate the choice by pressing 

ENTER. Confirming the selection returns the display to the previous SET screen. Cancelling 

the selection or pressing the BACK button returns the display to the SET screen.

NOTE: this parameter is available when in the system a heat pump enabled for room cooling 

is installed.

20,0

COOLING

°C

9.4 

Pre-heating

This function keeps the water in the domestic hot water exchanger hot, to reduce standby 

times when a request is made. When the preheating function is enabled, the symbol P 

comes on with a steady light at the top of the domestic hot water icon. During burner ignition 

following a preheating request, the symbol P starts flashing.

It is possible to access the PREHEATING function selecting 

SET

 on the main screen of 

the REC10H. Setting PREHEATING = 1 the boiler’s domestic hot water function activates. 

To deactivate the preheating function, set the parameter to PREHEATING = 0, the symbol 

P switches off. The function is not active when the boiler is OFF.

0

PREHEATING

CONFIRM OR DELETE SELECTION

CONFIRM

CANCEL

THE PARAMETER WILL BE 

CHANGED

9.5 

Touch&Go

If you do not want to leave the PREHEATING function always active and you need hot 

water ready immediately, it is possible to preheat the domestic water only a few moments 

before drawing. Set the parameter PREHEATING = 2 to activate the Touch & Go function. 

This function allows, by opening and closing the tap, to activate the instant preheating, which 

prepares the hot water only for that withdrawal.

2

PREHEATING

9.6 

Water tank setpoint

 

b

The parameter in question is available if pre-heating of the heat pump on the 

domestic hot water tank is present.

Press “

+

” and “

-

” to modify the domestic hot water setpoint stored in the water tank and heated 

by the heat pump and confirm with 

ENTER

.

Press 

BACK

 to return to the SET screen without making any selections.

Then you are asked to confirm the setpoint setting: select 

ENTER

 or 

BACK

 using “

+

” and “

-

” 

and validate the choice by pressing 

ENTER

.

Confirming the selection returns the display to the previous SET screen.

Canceling the selection or pressing the 

BACK

 button returns the display to the SET screen.

10  INFO

The 

INFO

 function can be used to display a series of data regarding the system.

ATTENTION

 - The displayed data cannot be modified.

SCREED HEATER OPERATING HOURS

DELIVERY PROBE

RETURN PROBE

DOMESTIC HOT WATER PROBE

HIGH STORAGE TANK PROBE

LOW STORAGE TANK PROBE

SOLAR COLLECTOR

FLUE GAS PROBE

OUTDOOR TEMPERATURE SENSOR

EXT T FOR THERMOREG

FLOW METER / DHW SETPOINT OT+

FAN

DELIVERY ZONE 1

DELIVERY ZONE 2

FLUE GAS PROBE OPERATING HOURS

MAIN ZONE SET-POINT

ZONE 1 SET-POINT

ZONE 2 SET-POINT

SYSTEM PRESSURE

HEAT PUMP DELIVERY

HEAT PUMP RETURN

HEAT PUMP EXT. TEMP.

TREFR LOW PRESSURE PIPE

TREFR HIGH PRESSURE PIPE

TREFR CONDENSER

TREFR HEAT EXCHANGER

 HEAT PUMP OPERATING MODE

HEAT PUMP FREQUENCY

HEAT PUMP COMPRESSOR TIME

HEAT PUMP CIRCULATOR TIME

HEAT PUMP FLOW SWITCH

HEAT PUMP OUTPUT

HEAT PUMP SET-POINT

NEXT ANTI-LEGIONELLA

The “

ENTER

” key is inactive. The “

BACK

” key allows you to return to the initial screen.

In the absence of additional zones or if the screed heater function is not operating, the 

relative information will not be displayed.

11  MENU

 

-

Select MENU 

 

SETTINGS or TIME SCHEDULE 

(available only if the timer is 

enabled (POR=1).

TIME SCHEDULE

SETTINGS

SELECT OPTION

MENU

11.1 

Settings

 

-

Select MENU 

 

SETTINGS 

 

  TIME&DATE (you can change HOURS, 

MINUTES, DAY, MONTH, YEAR) or DAYLIGHT SAVINGS TIME or LANGUAGE (to select 

the desired language) or BACKLIGHT.

TIME & DATE

LANGUAGE

SETTINGS

SELECT OPTION

BACKLIGHT

TIME & DATE

LANGUAGE

BACKLIGHT

SETTINGS

SELECT OPTION

TIME & DATE

DAYLIGHT SAVINGS TIME

ENTER TIME AND DATE

USE THE ARROWS TO MODIFY

12

17

09/04/2021

:

TIME & DATE

ENGLISH

LANGUAGE

SELECT LANGUAGE

ITALIANO

2

MIN

BACKLIGHT

SET THE INTERVAL OF TIME BEFORE AUTOMATIC 

SHUT-OFF OF THE SCREEN

11.1.1  Time&Date

Press “

ENTER

” to highlight in sequence HOURS, MINUTES, DAY, MONTH, YEAR and 

press the “

+

” and “

-

” keys to change the desired values. Save the settings by pressing 

ENTER

”; the display will return to the initial screen. By pressing “

BACK

” at any time the 

system will return to the SETTINGS cancelling the changes that were made.

11.1.2  Daylight savings time

By selecting FUNCTION ACTIVE the device automatically manages the change of time from 

solar to daylight savings time and vice versa.

11.1.3  Language

Press the “

+

” and “

-

” keys to select the desired language. Pressing “

ENTER

” the language 

selection is confirmed and the display returns to the initial screen. Pressing “

BACK

” the 

system returns to the SETTINGS screen without changing the system’s language.

11.1.4 

Backlight

Press the “

+

” and “

-

” keys to select the display lighting time. Save the setting by pressing 

ENTER

”; the display will return to the initial screen. By pressing “

BACK

” at any time the 

system will return to the SETTINGS cancelling the selection made.

After the set time has elapsed without any key being pressed, the anomaly report screen 

is displayed if the system is in alarm, or the backlight turns off, displaying only the clock.

In this case, the flame icon is also displayed if the burner is on and / or the heat pump icon 

if the latter is also operating. By pressing any key, the backlight turns on again, returning the 

display to the initial screen.

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...