START SCREEN

Upon ignition, the REC10CH might:

 

-

request the setting of the time and date (see “11.1 Settings”)

 

-

display the firmware version and require a button to be pressed in order to continue.

By pressing the “

+

” and “

-

” keys it is possible to move the selection of the functions in this 

order:  PLANT / STATE / SET / INFO / MENU.

By pressing the “

ENTER

” key you access the settings of the selected function (except for 

PLANT

). The “

BACK

” key is inactive (except for 

PLANT

).

The highlighted status is that which is currently selected.

42

°C

MENU

STATE

SET

INFO

HOT WATER TEMPERATURE

FRI

1.3 

bar

18/05/2013

12:17  

PLANT

7  PLANT

It indicates the zone to which the data shown on the start screen refer, and the zone to which 

the settings accessible via the other functions refer.

The presence of one or more zones in addition to PLANT depends upon the installa-

tion’s configuration. For this reason, one or more of the zones cited below may not be 

present in your configuration, or may be identified with a different name.

In order to change zones, highlight PLANT if necessary pressing the “

+

” and “

-

” keys. Then, 

pressing the “

ENTER

” and “

BACK

” keys, it will be possible to select the other zones in this 

sequence:

 

-

PLANT - MAIN ZONE - ZONE 1 - ZONE 2.

The TIME&DATE, DAYLIGHT SAVINGS TIME, LANGUAGE and BACKLIGHT settings 

are independent of the selected zone. The information contained in the INFO menu is 

independent of the selected zone.

No domestic hot water parameters can be set if MAIN, ZONE 1 or ZONE 2 is selected.

8  STATE

 

-

Select STATE 

 BOILER or MAIN ZONE or HEAT PUMP (if present).

BOILER

MAIN ZONE

STATE

HEAT PUMP

Note: MAIN ZONE is visible in this menu only if the zone is managed by a room thermostat.

HEAT PUMP is only visible if a heat pump is connected to the system.

8.1 

Boiler

 

-

Select STATE 

 BOILER 

  OFF  or HOT WATER ONLY (SUMMER) or 

HEATING AND HOT WATER (WINTER)

Once the selection has been validated, the display returns to the 

STATE

 screen.

OFF

HOT WATER ONLY

HEATING AND HOT WATER

BOILER

8.1.1 

OFF

If 

OFF

 is selected, the system shuts off. The electrical supply and the fuel supply remain active.

8.1.2 

WINTER

If 

HEATING AND HOT WATER

 is selected, the system produces domestic hot water and 

actives the heating function.

8.1.3 

SUMMER

If 

HOT WATER ONLY

 is selected, the system produces domestic hot water and, if a heat pump 

is configured, is also active the cooling function. Heating function is not active.

8.2 

Main zone

 

-

Select STATE 

 MAIN ZONE

-  if the heating programming timing is not enabled: ZONE ON - ZONE OFF

-  if the heating programming timing is enabled: AUTO - MANUAL - HEAT OFF.

ZONE ON

ZONE OFF

MAIN

AUTO

MANUAL

HEAT OFF

MAIN

Once the selection has been validated, the display returns to the 

STATE

 screen

.

8.2.1 

ON

If 

ON

 is selected, the zone requests are met.

8.2.2 

AUTO

If 

AUTO

 is selected, the zone requests will be managed based on a scheduled programme.

8.2.3 

MANUAL

If 

MANUAL

 is selected, the zone requests will be managed based on the setpoint set by 

the user.

8.2.4 

HEAT OFF

If 

HEAT OFF

 is selected, the zone requests will not be fulfilled.

NOTE

: to deactivate the zone in SUMMER or in WINTER, you must select the pre-set 

season (SUMMER or WINTER in the BOILER menu) and set the zone concerned to OFF.

8.3 

Heat pump (if present)

By selecting HEAT PUMP it is possible to enable the NIGHT REDUCTION. This parameter 

is used to reduce the noise of the heat pump by limiting the maximum operating frequency 

of the compressor in the time band set by the parameters NIGHT MODE START TIME and 

NIGHT MODE STOP TIME.

NIGHT MODE START TIME (if NIGHT REDUCTION is active)

This parameter is used to set the start time of the heat pump compressor frequency limitation 

band when the night reduction function is enabled. Range 00:00 - 23:30 / Default 22:00.

NIGHT MODE STOP TIME (if NIGHT REDUCTION is active)

This parameter is used to set the end time of the heat pump compressor frequency limitation 

band when the night reduction function is enabled. Range 00:00 - 23:30.

ENABLE NIGHT REDUCT

HEAT PUMP

DISABLE NIGHT REDUCT

NIGHT MODE START TIME

HEAT PUMP

NIGHT MODE STOP TIME

8.3.1 

Antilegio CUT OFF (only with water tank)

This function can be interrupted in advance in two different ways:

 

-

set the boiler to OFF 

or

 

-

select STATE 

 DHW 

ANTILEGIO CUTOFF.

If the function is interrupted, it will be repeated at the same time the next day, even if weekly 

programming is active.

BOILER

STATE

MAIN ZONE

BOILER

MAIN ZONE

STATE

DHW

STATE

DHW

ANTILEGIO CUT OFF

9  SET

 

-

Select SET 

 

HEATING or DHW

 or COOLING (if HP connected) or WATER TANK 

SETPOINT (if WATER TANK connected). or PREHEATING setpoints.

HEATING

COOLING

PREHEATING

SET

DHW

WATER TANK SETPOINT

9.1 

Heating

The user can change the heating setpoint by pressing the “

+

” and “

-

” keys.

When an outdoor temperature sensor is installed, the outlet temperature is automatically 

selected by the system, which quickly adjusts the ambient temperature according to the 

variations in the outdoor temperature. If you want to change the temperature, raising it or 

lowering it with respect to that automatically calculated by the electronic board, it is possible 

to change the HEATING setpoint selecting the desired comfort level within the range (-5 ÷ 

+5). The user is then asked to confirm the setpoint setting: select 

CONFIRM

 or 

CANCEL

 

and confirm. Once the selection is confirmed, the display returns to the 

SET

 screen. If the 

selection is cancelled or the “

BACK

” key is pressed you return to the previous 

SET

 screen.

CONFIRM OR DELETE SELECTION

CONFIRM

CANCEL

THE PARAMETER WILL BE 

CHANGED

SET

78,0

°C

HEATING

SET

9.2 

Hot water

The user can change the domestic hot water setpoint by pressing the “

+

” and “

-

” keys.

The user is then asked to confirm the setpoint setting: select 

CONFIRM

 or 

CANCEL

 and 

confirm. Once the selection is confirmed, the display returns to the 

SET

 screen. If the 

selection is cancelled or the “

BACK

” key is pressed you return to the previous 

SET

 screen.

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: