FAMILY

26

14  TECHNICAL DATA

DESCRIPTION

UM

FAMILY

25 KIS

30 KIS

35 KIS

G20

G31

G20

G31

G20

G31

CH

Rated heat input

kW-kcal/h

20,00 (****)-17.200

25,00-21.500

32,00-27.520

Nominal heat output (80°/60°)

kW-kcal/h

19,50-16.770

24,43-21.006

31,23-26.860

Nominal heat output (50°/30°)

kW-kcal/h

21,32-18.335

26,88-23.113

34,37-29.556

Reduced heat input 

kW-kcal/h

3,60-3.096

5,00-4.300

4,90-4.214

7,00-6.020

4,90-4.214

7,00-6.020

Reduced heat output (80°/60°) 

kW-kcal/h

3,46-2.975

4,82-4.145

4,68-4.024

6,75-5.803

4,69-4.037

6,75-5.803

Reduced heat output (50°/30°) 

kW-kcal/h

3,85-3.313

5,25-4.511

5,06-4.349

7,15-6.152

5,06-4.353

7,15-6.152

DHW

Rated heat input

kW-kcal/h

25,00 (****)-21.500

30,00-25.800

34,60-29.756

Nominal heat output (*)

kW-kcal/h

26,25-22.575

31,50-27.090

36,33-31.244

Reduced heat input 

kW-kcal/h

3,60-3.096

5,00-4.300

4,90-4.214

7,00-6.020

4,90-4.214

7,00-6.020

Reduced heat output (*)

kW-kcal/h

3,28-2.821

5,00-4.300

4,54-3.904

7,00-6.020

4,54-3.904

7,00-6.020

Useful efficiency Pn max - Pn min (80°/60°)

%

97,5 - 96,1

97,7 - 95,5

97,6 - 95,8

Combustion efficiency

%

97,8

97,9

97,8

Useful efficiency Pn max - Pn min (50°/30°)

%

106,6 - 107,0

107,5-103,2

107,4 - 103,3

Useful efficiency 30% Pn max (30° return)

%

109,1

109,5

109,5

Overall electric output (maximum CH-DHW output)

W

88 - 98

85 - 96

101 - 112

Circulator electric power (1.000 l/h) 

W

52

52

52

Category ● Country of destination

II2H3P 

● (+)

II2HY203P

 ● (+)

II2H3P 

● (+)

II2HY203P

 ● (+)

II2H3P 

● (+)

II2HY203P

 ● (+)

Voltage supply

V - Hz

230-50

230-50

230-50

Protection level

IP

X5D

X5D

X5D

Stop loss

W

30

26

26

Losses at the flue with burner off - burner on 

%

0,09 - 2,20

0,06 - 2,09

0,05 - 2,23

Heating operation

Maximum pressure - temperature

bar - °C

3 - 90

3 - 90

3 - 90

Minimum pressure for standard operation

bar

0,25 ÷ 0,45

0,25 ÷ 0,45

0,25 ÷ 0,45

Selection field of heating water temperature

°C

20/45 ÷ 40/80

20/45 ÷ 40/80

20/45 ÷ 40/80

Pump: maximum head available

mbar

410

410

410

for system capacity

l/h

1.000

1.000

1.000

Membrane expansion tank

l

10

10

10

Expansion tank pre-loading (heating)

bar

1

1

1

DHW operation

Maximum pressure

bar

8

8

8

Minimum pressure

bar

0,15

0,15

0,15

Quantity of hot water with 

Δt 25°C - 30°C - 35°C

l/min

15,1 - 12,5 - 10,8

18,1 - 15,1 - 12,9

20,8 - 17,4 - 14,9

DHW minimum capacity

l/min

2

2

2

Selection field of DHW temperature

°C

37-60

37-60

37-60

Flow regulator

l/min

10

12

14

Gas pressure

G20 G20.2

G31

G20 G20.2

G31

G20 G20.2

G31

Nominal methane gas pressure (G20 - I2H)

mbar

20

-

-

20

-

-

20

-

-

Nominal methane-hydrogen gas pressure (G20.2 - I2Y20)

mbar

-

20

-

-

20

-

-

20

-

Nominal liquid gas LPG pressure (G31 - I3P)

mbar

-

-

37

-

-

37

-

-

37

Central heating capacity

Air capacity

Nm

3

/h

24,298

24,819

30,372

31,024

38,876

39,710

Flue gas capacity

Nm

3

/h

26,304

26,370

32,880

32,963

42,086

42,192

Mass flue gas flow rate (max-min)

g/s

9,086-1,635

9,297-2,324 11,357-2,226 11,621-3,254 14,537-2,226 14,875-3,254

Domestic hot water capacity

Air capacity

Nm

3

/h

30,372

31,024

36,447

37,228

42,035

42,937

Flue gas capacity

Nm

3

/h

32,880

32,963

39,456

39,555

45,506

45,620

Mass flue gas flow rate (max-min)

g/s

11,357-1,635 11,621-2,324 13,629-2,226 13,946-3,254 15,718-2,226 16,084-3,254

Fan performance

Residual discharge head of concentric pipes 0.85 m

Pa

60

60

60

Residual discharge head of separate pipes 0.5 m

Pa

174

150

190

Residual discharge head of boiler without pipes

Pa

180

170

195

NOx

class 6

class 6

class 6

Emission values at maximum and minimum output (**)
Max-Min

CO s.a. less than

p.p.m.

130 - 10

130 - 10

120 - 10

140 - 10

170 - 10

160 - 10

CO2 (***)

%

9,0 - 9,0

10,0 - 10,0

9,0 - 9,0

10,0 - 10,0

9,0 - 9,0

10,0 - 10,0

NOx s.a. lower than

p.p.m.

30 - 30

30 - 30

50 - 25

50 - 50

50 - 25

50 - 40

T flue gases

°C

69 - 63

68 - 62

67 - 59

65 - 59

64 - 65

67 - 63

(*) average value between various hot water operation conditions - (**) Check performed with concentric pipe Ø 60-100, length 0.85 m. - water temperature 80-60°C.- (***) tolerance CO2 +0.6% -1% - 

(****) The rated heat input with gas G20.2 (I2Y20) undergoes a reduction: Rated heat input heating = 18,9kW; Rated heat input DHW = 23,1kW

The data indicated must not be used to certify the system; for certification, use the data indicated in the “System handbook” measured during first ignition.

(+)  The installation of this product is allowed only in the destination Countries contained in the data plate, regardless of the present translation language.

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: