Table of adjustments INSIDE CHIMNEY PIPES

 

twin flue pipe

Fan rotations rpm

Pipes Ø50 

Pipes

 Ø60 

Pipes Ø80 

∆P 

at boiler outlet

CH

DHW

Maximum length (m)

25 KIS

6.200

7.600

5

18

98

174

6.300

7.700

7 *

23 *

125 *

213

6.400

7.800

9 *

28 *

153 *

253

6.500

7.900

11 *

33 *

181 *

292

6.600

8.000

13 *

38 *

208 *

332

6.700

8.100

15 *

43 *

236 *

371

6.800

8.200

17 *

48 *

263 *

410

6.900

8.300

19 *

53 *

291 *

450

7.000

8.400

22 *

58 *

319 *

489

7.100

8.500

24 *

63 *

346 *

528

30 KIS

5.800

6.900

2

11

53

150

5.900

7.000

4 *

15 *

73 *

189

6.000

7.100

5 *

19 *

93 *

229

6.100

7.200

7 *

24 *

113 *

268

6.200

7.300

9 *

28 *

133 *

308

6.300

7.400

10 *

32 *

153 *

347

6.400

7.500

12 *

36 *

173 *

386

6.500

7.600

14 *

40 *

193 *

426

6.600

7.700

16 *

44 *

214 *

465

6.700

7.800

17 *

49 *

234 *

504

35 KIS

7.300

7.800

2

11

57

190

7.400

7.900

3 *

15 *

75 *

229

7.500

8.000

4 *

19 *

93 *

269

7.600

8.100

6 *

22 *

112 *

308

7.700

8.200

7 *

26 *

130 *

348

7.800

8.300

9 *

30 *

148 *

387

7.900

8.400

10 *

33 *

166 *

426

8.000

8.500

12 *

37 *

184 *

466

8.100

8.600

13 *

40 *

202 *

505

8.200

8.700

15 *

44 *

220 *

544

(*)  Maximum length that can be installed ONLY with class H1 discharge pipes.

The Ø50 or Ø60 or Ø80 configurations contain Lab test data. In the event of installations that 

differ from the indications in the “standard configurations” and “adjustments” tables, refer to 

the equivalent linear lengths below.

 

b

In any case, the maximum lengths declared in the booklet are guaranteed, and it is 

essential not to exceed them.

Linear equivalent in metres Ø80 (m)

COMPONENT

Ø 50

Ø 60

Bend 45°

12.3

5

Bend 90°

19.6

8

Extension 0.5m

6.1

2.5

Extension 1.0m

13.5

5.5

Extension 2.0m

29.5

12

   

 

chimney for ducting 

Ø 50 mm or Ø 60 mm 

or Ø 80 mm

length

90° bends 

Ø 80 mm

Ø 80 mm

4,5 m Ø 80 mm

Ø 80-60 mm 

or Ø 80-50 mm 

reduction

90° bend 

Ø 50 mm 

Ø 60 mm 

or Ø 80 mm

2.8 

Installation on collective flues in positive pressure

The collective flue is a flue gas exhaust system suitable for collecting and expelling the 

combustion products of several appliances installed on several floors of a building.

The positive pressure collective flues can only be used for type C condensing appliances. 

Therefore  the  B53P/B23P  configuration  is  forbidden.  The  installation  of  boilers  under 

collective  pressure  flues  is  allowed  exclusively  in  G20.  The  boiler  is  sized  to  operate 

correctly up to a maximum internal pressure of the flue no higher than the value of 25 Pa. 

Check that the fan speed corresponds to what is shown in the “technical data” table.

Make sure that the air intake and exhaust pipes of the combustion products are watertight.

WARNINGS:

 

b

The appliances connected to a collective pipe must all be of the same type and have 

equivalent combustion characteristics.

 

b

The number of devices connected to a positive pressure collective pipe is defined 

by the flue designer

.

The boiler is designed to be connected to a collective flue sized to operate in conditions 

where the static pressure of the collective flue pipe can exceed the static pressure of the 

collective air duct of 25 Pa in the condition in which n-1 boilers work at maximum rated heat 

input and 1 boiler at the minimum rated heat input allowed by the controls.

 

b

The minimum permissible pressure difference between the flue gas outlet and the 

combustion air inlet is -200 Pa (including - 100 Pa of wind pressure).

For both types of exhaust, further accessories are available (curves, extensions, terminals, 

etc.) which make possible the flue gas exhaust configurations foreseen in the boiler booklet.

 

b

The pipes must be installed in such a way as to avoid condensation sticking which 

would prevent the correct evacuation of the combustion products.

 

b

A data plate must be present at the connection point with the collective flue pipe. 

The plate must include at least the following information:

 

-

the collective flue is sized for boilers C(10) type

 

-

the maximum permissible mass flow of the combustion products in kg/h

 

-

the dimensions of the connection to the common pipes

 

-

a warning concerning the openings for the air outlet and the entry of the combu-

stion products of the collective pressure pipe; these openings must be closed and 

their tightness must be checked when the boiler is disconnected

 

-

the name of the manufacturer of the collective smoke pipe or its identification 

symbol.

 

b

See applicable legislation for the discharge of the combustion products as well as 

local regulations.

 

b

The flue gas pipe must be suitably selected based on the parameters shown below

.

maximum length

minimum length

UM

ø 60-100

4,5

0,5

m

ø 80

4,5

0,5

m

ø 80/125

4,5

0,5

m

 

b

The terminal of the collective pipe must generate an upward air current.

 

b

Before attempting any operation, disconnect the appliance from the electrical supply.

 

b

Before assembling, lubricate the gaskets with a non-corrosive glide lubricant.

 

b

The flue gases discharge pipe should be inclined, if the pipe is horizontal, by 3° 

towards the boiler.

 

b

The number and characteristics of the exhaust ventilation devices which are the real 

characteristics of the flue itself.

 

b

The condensation can flow inside the boiler.

 

b

The maximum recirculated value allowed in wind conditions is 10%.

 

b

The maximum permissible pressure difference (25 Pa) between the combustion 

products inlet and the air outlet of a collective flue can not be exceeded when-

1 boiler work at the maximum nominal heat output and 1 boiler within minimum 

temperature allowed by the checks.

 

b

The collective smoke pipe must be adequate for an overpressure of at least 200 Pa.

 

b

The collective flue must not be equipped with a wind-proofing device.

At this point it is possible to install the curves and extensions, available as accessories, 

depending on the type of installation desired.

The maximum permissible lengths of the flue pipe and the air intake pipe are given in the 

section “2.7 Flue gas exhaust and combustion air suction”.

With C(10) installation, in any case, report the number of fan speed (rpm) on the 

label placed next to the data plate.

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: