15

ENGLISH

EN

WINTER 

/

:

  select STATE 

 BOILER 

  HEATING AND HOT WATER 

(WINTER)  to activate heating and domestic hot water functions

.

 The REC10CH normally 

displays the domestic hot water temperature unless there is a heating request in progress, 

in which case the boiler’s outlet temperature is displayed. 

OFF

HOT WATER ONLY

HEATING AND HOT WATER

BOILER

4.4 

Adjusting the heating water temperature without an outdoor 

temperature sensor connected

The HEATING setpoint can be set by selecting SET in the REC10CH main screen and choosing 

[40°C ÷ 80.5°C] for high temperature systems and [20°C ÷ 45°C] for low temperature systems.

HEATING

HOT WATER

PREHEATING

SET

4.5 

Adjusting the heating water temperature with an outdoor 

temperature sensor connected

The outlet temperature value is automatically chosen by the system, which rapidly adjusts 

the room temperature according to the variations in the external temperature.To modify the 

temperature value, increasing or decreasing it with respect to that automatically calculated 

by the electronic board, it is possible to act on the HEATING setpoint by selecting SET in 

the REC10CH main screen and choosing the desired comfort level within the range (-5 

÷ +5) (see section “4.2.4 Setting the thermoregulation”). Note: when there is an outdoor 

temperature sensor connected it is still possible to have the boiler operate at a fixed point 

setting the values of MIN SP HEAT and MAX SP HEAT at the desired HEATING setpoint. 

4.6 

Adjusting the domestic hot water temperature 

 

To set the domestic hot water temperature (bath, shower, kitchen, etc.):  SET 

  HOT 

WATER to choose the desired value between the range [37,5°C ÷ 60°C].

HEATING

HOT WATER

PREHEATING

SET

4.7 

“Preheating” function 

 

Access to SET 

 PREHEATING menu to activate this function.

Setting PREHEATING = 1 the boiler’s domestic hot water function activates. This function 

keeps the water in the domestic hot water exchanger hot, to reduce standby times when 

a request is made. When the pre-heating function is enabled, the symbol P comes on with 

a steady light at the top with respect to the hot water icon. During burner ignition following 

a pre-heating request, the symbol P starts flashing. However, setting the parameter 

PREHEATING = 2 activates the Touch&Go function, the boiler carries out, only if necessary, 

just one pre-heating cycle after each take of domestic hot water. To deactivate the pre-

heating function, set the parameter to PREHEATING = 0, the symbol “P” switches off. The 

function is not active when the boiler is OFF.

HEATING

DHW

PREHEATING

SET

4.8 

Boiler start-up

If there is a room thermostat or a programming timer, or the REC10CH MASTER is set as 

an ambient regulator, it is necessary that these are on and that they have been adjusted 

to a temperature higher than the ambient temperature so that the boiler switches on. The 

boiler will be in standby until the burner switches on following a heat request. The display 

shows 

 to indicate the presence of a flame.

42

°C

MENU

STATE

SET

INFO

HOT WATER TEMPERATURE

FRI

1.3 

bar

18/05/2013

12:17  

PLANT

The boiler will be in function until the selected temperature is reached, afterwards it will 

be in “standby” again keeping the outlet temperature displayed. If faults arise in ignition or 

operations, the boiler performs a “SAFETY STOP”: the triangle signalling faults will flash on 

the REC10CH. To identify the fault codes and to reset the appliance, see the section “4.14 

Lights and faults”.

E010

OK/ENTER TO RESET

FLAME LOCKOUT

4.9 

Reset function

In the event of a lockout, it is possible to try and reset normal operations by pressing “ENTER” 

on the REC10CH when the fault message is displayed to reset the alarm in progress.

 

b

If the release attempts do not restart the boiler, contact your local Technical 

Assistance Centre.

4.10  Screed heater function

For a low temperature system the boiler has a “screed heater” function that can be activated 

in the following way:

 

-

set the boiler to OFF 

 

-

select SCREED HEATING (Note: SCREED HEATING is not available if the boiler is not OFF)  

 FUNCTION ACTIVE or FUNCTION NOT ACTIVE and confirm to enable /disable 

the function.

RANGE RATED

CALIBRATION

COMBUSTION ANALYSIS

SCREED HEATING

EXHAUST PROBE RESET

INSTALLER

TECHNICAL

FUNCTION ACTIVE

FUNCTION NOT ACTIVE

INSTALLER

SCREED HEATING

The screed heater function, when active, is signalled on the main screen by the scrolling 

message at the bottom of the SCREED HEATING FUNCTION IN PROGRESS - OUTLET 

TEMPERATURE page. The “screed heater” function lasts 168 hours (7 days) during 

which, in the zones configured as low temperature, a heating request is simulated with an 

initial zone outlet of 20°C, then increased in line with the table on the side. Accessing the 

INFO menu from the main page of the REC10CH it is possible to display the TIME FUNC 

SCREED HEATING value regarding the number of hours since the start of the function. 

Once activated, the function takes priority, if the machine is shut down by disconnecting 

the power supply, when it is restarted the function picks up from where it was interrupted. 

The function can be interrupted before its end by putting the machine in a condition other 

than OFF or else by selecting DEACTIVATE FUNCTION from the relative menu. 

Note

: The 

temperature and increase values can be set to different values only by qualified personnel, 

only if strictly necessary. The manufacturer declines all responsibility if the parameters are 

incorrectly set.

DAY

TIME

TEMPERATURE

1

0

20°C

6

22°C

12

24°C

18

26°C

2

0

28°C

12

30°C

3

0

32°C

4

0

35°C

5

0

35°C

6

0

30°C

7

0

25°C

4.11 

Checks during and after the first commissioning

After starting up, check that the boiler carries out the start-up procedures and subsequent 

shut-down properly. Check the domestic hot water operation by opening a hot water tap 

in SUMMER mode or WINTER mode. Check the full stop of the boiler by turning off the 

system’s main switch. After a couple of minutes of continuous operation to be obtained 

by turning the system’s main switch to “on”, setting the boiler mode selector to Summer 

and by keeping open the domestic hot water device, the binders and manufacturing waste 

evaporate and it will be possible to carry out:

-  checking the combustion.

OFF

HOT WATER ONLY

HEATING AND HOT WATER

BOILER

4.12  Combustion check

To carry out the combustion analysis, proceed as follows:

 

-

power the boiler electrically by setting the main system switch to “ON”

 

-

set the boiler to OFF 

 

-

select TECHNICAL 

 COMBUSTION ANALYSIS 

 ACTIVATE FUNCTION 

and confirm

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: