Only for installer:

 At the end of the procedure, proceed with the automatic vent cycle as 

described in “Filling the heating system and eliminating air”.

A

 

b

If the drop in pressure is very frequent, contact the Technical Assistance Centre.

For fault E060:

 

the boiler is working normally, but does not provide any stability of the 

domestic hot water temperature that, in any event, is supplied at a temperature of around 

50°C. The intervention of the Technical Assistance Service is required.

For fault E091: 

the boiler has an auto-diagnostic system which, based on the total number 

of hours in certain operating conditions, can signal the need to clean the primary exchanger 

(alarm code E091). Once the cleaning operation has been completed, reset to zero the total 

hour meter with special kit supplied as an accessory following procedure indicated below:

 

-

select TECHNICAL 

 EXHAUST PROBE RESET 

 CONFIRM or BACK.

CONFIRM OR DELETE SELECTION

CONFIRM

CANCEL

THE PARAMETER WILL BE 

CHANGED

RANGE RATED

CALIBRATION

WEATHER COMPENSATION

COMBUSTION ANALYSIS

EXHAUST PROBE RESET

INSTALLER

TECHNICAL

Note:

 The meter resetting procedure should be carried out after each in-depth cleaning of 

the primary exchanger or if this latter is replaced.

The total hours can be verified in the following way: INFO menu  

 FLUE GAS PROBE  

 press “

ENTER

” to display the value of the flue gases probe meter 

30

°C

.3

MENU

STATE

SET

INFO

HOT WATER TEMPERATURE

FRI

1.3 

bar

18/05/2013

12:17

PLANT

Boiler faults list

ERROR CODE

ERROR MESSAGE

DESCRIPTION OF TYPE OF ALARM

E010

flame lockout/ACF electronic fault

definitive

E011

extraneous flame

transitional

E020

limit thermostat

definitive

E030

fan fault

definitive

E040

water transducer - load system

definitive

E041

water transducer - press ENTER to fill the system

transitional

E042

water pressure transducer fault

definitive

E060

domestic hot water probe fault

transitional

E070

flow sensor faulty 

 flow sensor overtemperature 

 flow/return sensor differential alarm

transitional 

 

definitive 

 definitive

E077

main zone water thermostat

transitional

E080

return line probe fault 

 return line probe overtemperature 

 outlet/return line probe differential alarm

transitional 

 

definitive 

 definitive

E090

flue gas probe faulty 

 flue gas probe overtemperature

transitional 

 

definitive

E091

clean primary heat exchanger

transitional

E099

reset attempts exhausted, boiler blocked

definitive, not resettable

--

water pressure low press ENTER to charge

transitional

--

water pressure high check system

transitional

--

boiler board communication lost

transitional

--

BUS 485 communication lost

transitional

List of combustion faults

ERROR CODE

ERROR MESSAGE

DESCRIPTION OF TYPE OF ALARM

E021

ACC monitor error

These are temporary alarms that if they occur several times

 in an hour they become definitive; the alarm E097 is displayed and is 

followed by post-purging for 45 seconds at the fan's maximum speed.

It is always possible to release the alarm before the end of the post-purging.

E022

ACC monitor error

E023

ACC monitor error

E024

ACC monitor error

E067

ACC monitor error

E088

ACC monitor error

E097

ACC monitor error

E085

incomplete combustion

These are temporary alarms that if they occur several times

 in an hour they become definitive; the last error to occur is displayed 

and is followed by a post-purging of 2 minutes at the fan's maximum speed. It is not possible to release the alarm before the end of 

the post-purging unless the boiler's power supply is switched off.

E094

incomplete combustion

E095

incomplete combustion

E058

mains voltage fault

These are temporary faults that restrict the ignition cycle.

E065

current modulation alarm

E086

flue gases obstruction alarm

Temporary fault signalled during Pre-Purging. Post-Purging is maintained for 5 min at maximum fan speed.

Содержание 20187642

Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Страница 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Страница 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Страница 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Страница 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Страница 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Страница 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Страница 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Страница 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Страница 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Страница 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Страница 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Страница 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Страница 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Страница 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Страница 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Страница 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Страница 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Страница 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Страница 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Страница 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Страница 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Страница 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Страница 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Страница 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Страница 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Страница 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Страница 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Страница 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Страница 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Страница 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Страница 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Cod 20187595 09 21 Ed 3...

Отзывы: