Only for installer:
At the end of the procedure, proceed with the automatic vent cycle as
described in “Filling the heating system and eliminating air”.
A
b
If the drop in pressure is very frequent, contact the Technical Assistance Centre.
For fault E060:
the boiler is working normally, but does not provide any stability of the
domestic hot water temperature that, in any event, is supplied at a temperature of around
50°C. The intervention of the Technical Assistance Service is required.
For fault E091:
the boiler has an auto-diagnostic system which, based on the total number
of hours in certain operating conditions, can signal the need to clean the primary exchanger
(alarm code E091). Once the cleaning operation has been completed, reset to zero the total
hour meter with special kit supplied as an accessory following procedure indicated below:
-
select TECHNICAL
EXHAUST PROBE RESET
CONFIRM or BACK.
CONFIRM OR DELETE SELECTION
CONFIRM
CANCEL
THE PARAMETER WILL BE
CHANGED
RANGE RATED
CALIBRATION
WEATHER COMPENSATION
COMBUSTION ANALYSIS
EXHAUST PROBE RESET
INSTALLER
TECHNICAL
Note:
The meter resetting procedure should be carried out after each in-depth cleaning of
the primary exchanger or if this latter is replaced.
The total hours can be verified in the following way: INFO menu
FLUE GAS PROBE
press “
ENTER
” to display the value of the flue gases probe meter
30
°C
.3
MENU
STATE
SET
INFO
HOT WATER TEMPERATURE
FRI
1.3
bar
18/05/2013
12:17
PLANT
Boiler faults list
ERROR CODE
ERROR MESSAGE
DESCRIPTION OF TYPE OF ALARM
E010
flame lockout/ACF electronic fault
definitive
E011
extraneous flame
transitional
E020
limit thermostat
definitive
E030
fan fault
definitive
E040
water transducer - load system
definitive
E041
water transducer - press ENTER to fill the system
transitional
E042
water pressure transducer fault
definitive
E060
domestic hot water probe fault
transitional
E070
flow sensor faulty
•
flow sensor overtemperature
•
flow/return sensor differential alarm
transitional
•
definitive
•
definitive
E077
main zone water thermostat
transitional
E080
return line probe fault
•
return line probe overtemperature
•
outlet/return line probe differential alarm
transitional
•
definitive
•
definitive
E090
flue gas probe faulty
•
flue gas probe overtemperature
transitional
•
definitive
E091
clean primary heat exchanger
transitional
E099
reset attempts exhausted, boiler blocked
definitive, not resettable
--
water pressure low press ENTER to charge
transitional
--
water pressure high check system
transitional
--
boiler board communication lost
transitional
--
BUS 485 communication lost
transitional
List of combustion faults
ERROR CODE
ERROR MESSAGE
DESCRIPTION OF TYPE OF ALARM
E021
ACC monitor error
These are temporary alarms that if they occur several times
in an hour they become definitive; the alarm E097 is displayed and is
followed by post-purging for 45 seconds at the fan's maximum speed.
It is always possible to release the alarm before the end of the post-purging.
E022
ACC monitor error
E023
ACC monitor error
E024
ACC monitor error
E067
ACC monitor error
E088
ACC monitor error
E097
ACC monitor error
E085
incomplete combustion
These are temporary alarms that if they occur several times
in an hour they become definitive; the last error to occur is displayed
and is followed by a post-purging of 2 minutes at the fan's maximum speed. It is not possible to release the alarm before the end of
the post-purging unless the boiler's power supply is switched off.
E094
incomplete combustion
E095
incomplete combustion
E058
mains voltage fault
These are temporary faults that restrict the ignition cycle.
E065
current modulation alarm
E086
flue gases obstruction alarm
Temporary fault signalled during Pre-Purging. Post-Purging is maintained for 5 min at maximum fan speed.
Содержание 20187642
Страница 1: ...Family KIS EN INSTALLER AND USER MANUAL...
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ...Cod 20187595 09 21 Ed 3...